Maintenance/adjustment – MMD Equipment 150S-6A6 User Manual

Page 57

Advertising
background image

6. Maintenance/Adjustment

6-4

Symptom Cause Counter

measures

Even when
operated at a rated
speed, no voltage
or too low voltage
generated.



(1) Faulty voltmeter
(2) Poor tightening of terminals
(3) Broken or short-circuited winding of

generator main unit

(4) Faulty AVR
(5) Faulty silicon rectifier (mounted on

generator rotor)

(6) Faulty exciter
(7) Broken or short-circuited circuit to

exciter field winding

(8) AVR frequency selection switch is not set

to meet the frequency to be operated.

(9) Function circuit protector (CP) for AVR

protection

Check/change
Check/repair
Check/repair

Check/change
Check/change

Check/repair

Check/repair

Check/select

Reset

Too high voltage
generated when
set at the rated
frequency
(50Hz/60Hz),
Voltage will not
drop even when
the voltage
regulator
controlling knob is
turned.

(1) Loosened or disconnected wiring, or

connector to AVR

(2) Faulty AVR
(3) Broken wire or poor contact of AVR

variable resistor

Check/repair

Check/change

Repair or change

Unstable voltage
generation

(1) Poor tightening of each terminal
(2) Faulty AVR
(3) Function circuit protector (CP) for AVR

protection

Check/repair
Check/change

Reset

Please contact your nearest dealer if you find it difficult to repair by yourselves.

Please refer to the engine operation manual for troubles concerning the engine.