H*34DF Indoor Gas Fireplace

Page 18

XG0146 - 150204

Installation

Installing a Wall Mounted RHS7 Heat shield

The RHS7 Heat shield CANNOT be used WITHIN 36" horizontal or

60" vertically of the fireplace, (see figure 18a). For applications within

these dimensions the RHS100 Heat Shield MUST be used.
To install the RHS7, frame an opening in combustible construction,

Figure 18 below. Slide the Heat shield in place over the vent pipe

which attaches to the fireplace. After the fireplace and vent pipe has

been installed, clearances should match the dimensions in Figure 18.

Figure 18. RHS7 Installation. (Install by sliding over vent pipe where it passes

through the combustible construction).

Figure 18a. RHS7 Installation. (Minimum requirements).

Figure 19. RHS100 Installation. (Install by sliding Outer Section over vent pipe

where it passes through the combustible construction.

Figure 19a. Heat Shield. After sliding the outer section in place.

Installing a Wall Mounted RHS100 Heat shield.

The RHS100 Heat shield MUST be used where the RHS7 Termination

(Figure 18 and 18a) CANNOT be used. Use the RHS100 within 36"

horizontal or 60" vertical.
To install the RHS100, Slide the Inner Section over the vent pipe that will

connect to the fireplace. Fasten the vent pipe to the back of the fireplace

with a Min. of three sheet metal screws.
Next, slide the RHS100 outer section from the outside of the structure,

see Figure 19.
To complete the installation fasten the Heat Shield Outer Section &

Termination frame to the structure Figure 19a.

Figure 19b.

RHS100 Installation.

RHS7 Heat Shield

1” Min. Both sides Typical

1” Min.

1” Min.

Combustible Framing

Outer Shield

3/8” Min. Both sides Typical

3/8” Min.

3/8” Min .

Combustible Framing

Inner Shield

Combustible

framing

Termination

Drywall / sheetrock
RHS100 Heat Shield, inner Section

RHS100 Heat Shield

Outer Section

Vent pipe, from fireplace

Termination

Drywall / sheetrock
RHS100 Heat Shield, inner Section

RHS100 Heat Shield

Outer Section

RHS7 Heat

Shield

36” Min

60” Min.

Note: Images are shown without screens for clarity purposes. However,

your fireplace should not be operated without proper installation of

screens.