Installation – Montigo PVVEX58-300 User Manual

Page 10

Advertising
background image

PVVEX58-300 & PVVEX510-300 Horizontal Power Vent

Page 10

XG0518 - 070714

* Based on CGA B149.1 Natural Gas and Propane installation code. Local codes may vary, please check with local regulatory agency.

** Based on ANSI Z223.1/NFPA 54 National Fuel Gas Code. Local codes may vary, please check with local regulatory agency.

+ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serve both dwellings.

++ Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

V

Vertical Detail

Horizontal

Detail

Location

Canada*

USA**

A

clearance to the termination frame above grade, veranda, porch, deck, or balcony

30 inches

30 inches

B

clearance to top of doors or operable windows

12 inches

12 inches

C

clearance to sides or bottom of door or operable windows

4 feet

4 feet

D

clearance to permanently closed window when installed with approved glass penetration termination

0

0

E

clearance to permanently closed window Recommended to prevent condensation

30 inches

30 inches

F

clearance to ventilated soffit located within a horizontal distance to 24 inches from centerline
of termination

22 inches

22 inches

G

clearance to unventilated soffit

30 inches

30 inches

H

clearance to outside corner

30 inches

30 inches

I

clearance to inside corner

30 inches

30 inches

J

clearance to each side of the vertical centerline of a metre or regulatory assembly to a maximum

vertical distance of 15ft

3 feet

3 feet

K

clearance to service regulator vent outlet

3 feet

3 feet

L

clearance to non mechanical air supply inlet to the building or combustion air inlet to other
appliance for appliance <= 100.000 BTU/H (30 KW)

12 inches

4 feet

L

clearance to non mechanical air supply inlet to the building or combustion air inlet to other
appliance for appliance > 100.000 BTU/H (30 KW)

6 feet

4 feet

M

clearance to forced air supply inlet

6 feet

3 feet above air inlet

N+ clearance above paved sidewalk or paved driveway located on public property

7 feet

7 feet

P++ clearance under veranda, porch, deck, or balcony

30 inches

30 inches

Q

clearance above roof

See Fireplace Installation Guide

See Fireplace Installation Guide

R

clearance to adjacent walls and neighboring buildings

See Fireplace Installation Guide

See Fireplace Installation Guide

S

clearance from corner in recessed location

30 inches

30 inches

T

Maximum depth of recessed location

48 inches

48 inches

U

Maximum width for back wall of recessed location

60 inches

60 inches

V

Horizontal clearance between two terminations that are level

See Fireplace Installation Guide

See Fireplace Installation Guide

W

Horizontal clearance (centre to centre) between two terminations that are not level

30 inches

30 inches

Power Vent Locations

Installation