ONICON D-100 Dualnet User Manual

Page 20

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

D-100 Dual Network Interface Installation Guide 07/14 - 1015

Page 20

Networking Information

MODBUS RTU

MODBUS TCP

Connection Information

RS485, 2-wire half-duplex

Base 10T, 10Mbps, RJ 45 Connection

Data format / Parity

8 bits, 1 stop bit / None

8 bits, 1 stop bit / None

Flow Control (handshaking)

None

None

Device Address Range

1 - 247

1 - 247

IP Address

Not required

Default address: 192.168.1.24

Termination (selectable)

120 W or none (default none)

None

Biasing

None

None

3.2 MODBUS MEMORY MAP TABLE

Available Engineering Units

Engineering Units

Abbreviation

Volume Rate (Flow)
Gallons per minute

GPM

Gallons per minute x 10

GPM x 10

Gallons per hour

GPH

Million gallons per day

MGD

Liters per second

L/S

Liters per minute

L/M

Liters per hour

L/Hr

Cubic meters per hour

M³/Hr

Cubic meters per hour x 10

M³/Hr x 10

Cubic Feet per second

Ft³/S

Cubic Feet per minute

Ft³/M

Mass Rate (Mass Flow) –

Only available with F-2000 Flow Meter
Pounds per hour

Lb/Hr

Pounds per hour x 10

Lb/Hr x 10

Kilograms per hour

kg/Hr

Kilograms per hour x 10

kg/Hr x 10

Temperature
Degrees Fahrenheit

°F

Degrees Celsius

°C

Generic

None

Engineering Units

Abbreviation

Volume Total

Gallons x 1,000

kGal

Gallons x 1,000,000

MGal

Gallons x 1,000,000,000

GGal

Liters x 1,000

kLiters

Liters x 1,000,000

MLiters

Liters x 1,000,000,000

GLiters

Cubic Meters

Cubic Meters x 1,000

kM³

Cubic Feet

Ft³

Mass Total -

Only available with F-2000 Flow Meter
Pounds x 1,000

kLbs

Pounds x 1,000,000

MLbs

Kilograms x 1,000

Kkg

Kilograms x 1,000,000

Mkg

Advertising