ONICON D-100 Dualnet User Manual

Page 5

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

D-100 Dual Network Interface Installation Guide 07/14 - 1015

Page 5

1.3 SPECIFICATIONS

RS485 (BACnet MS/TP or MODBUS RTU)

Transceiver: 2-wire, half-duplex

Baud rate: 9600, 19200, 38400 & 76800

Termination: 120 ohms or none (Default: none)

Biasing: None

Flow control: None

BACnet UDP/IP & MODBUS TCP/IP

Transceiver: 10Base T, 10Mbps, Rj45 connection

Default IP address: 192.168.1.24

Default Subnet Mask: 255.255.255.0

BACnet Port: 47808

MODBUS Port: 502

Flow control: None

Address Ranges

MODBUS device address range: 1 – 127 (Default: 017)

BACnet device address range: 1 – 127 (Default: 017)

BACnet Device Instance range: 0 - 4,194,303 (Default: 57017)

SECTION 1: INTRODUCTION

1.1 PURPOSE OF THIS GUIDE

The purpose of this guide is to provide installation and commissioning procedures and basic

operating and servicing instructions for the ONICON D-100 Dual Network Flow Display

Network Interface.

1.2 TYPICAL D-100 NETWORK INTERFACE MODULE

The D-100 is a totalizing display module that provides a local indication of liquid, gas or

steam flow rate and total data. It can also be configured with an optional network interface

to communicate data to the building control network. It is housed in a steel wall mounted

enclosure with a built-in user interface/display.

Steam

Building

Domestic Water Supply

Flow rate and total data to

Data Acquisition System or

Building Control System

120VAC or 24VAC

Input Voltage

BACnet and/or MODBUS

COMMUNICATIONS

TO NETWORK

Local display of

flow data