ONICON D-100 Dualnet User Manual

Page 21

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

D-100 Dual Network Interface Installation Guide 07/14 - 1015

Page 21

Register

Address

Description

Register Type

Read/Write

Comment

41009

Volume Rate – GPM

Floating point register (1 of 2)

Read Only

41010

Volume Rate – GPM

Floating point register (2 of 2)

Read Only

41011

Volume Rate – GPH

Floating point register (1 of 2)

Read Only

41012

Volume Rate – GPH

Floating point register (2 of 2)

Read Only

41013

Volume Rate – MGD

Floating point register (1 of 2)

Read Only

41014

Volume Rate – MGD

Floating point register (2 of 2)

Read Only

41015

Volume Rate – L/S

Floating point register (1 of 2)

Read Only

41016

Volume Rate – L/S

Floating point register (2 of 2)

Read Only

41017

Volume Rate – L/M

Floating point register (1 of 2)

Read Only

41018

Volume Rate – L/M

Floating point register (2 of 2)

Read Only

41019

Volume Rate – L/Hr

Floating point register (1 of 2)

Read Only

41020

Volume Rate – L/Hr

Floating point register (2 of 2)

Read Only

41021

Volume Rate – M³/Hr

Floating point register (1 of 2)

Read Only

41022

Volume Rate – M³/Hr

Floating point register (2 of 2)

Read Only

41071

Volume Rate – Ft³/S

Floating point register (1 of 2)

Read Only

41072

Volume Rate – Ft³/S

Floating point register (2 of 2)

Read Only

41073

Volume Rate – Ft³/M

Floating point register (1 of 2)

Read Only

41074

Volume Rate – Ft³/M

Floating point register (2 of 2)

Read Only

41023

Mass Rate – Lb/Hr

Floating point register (1 of 2)

Read Only

Mass units are only

available when using

F-2000 Vortex Meter.

41024

Mass Rate – Lb/Hr

Floating point register (2 of 2)

Read Only

41025

Mass Rate – Kg/Hr

Floating point register (1 of 2)

Read Only

41026

Mass Rate – Kg/Hr

Floating point register (2 of 2)

Read Only

41027

Supply Temperature – °F

Floating point register (1 of 2)

Read Only

41028

Supply Temperature – °F

Floating point register (2 of 2)

Read Only

41029

Return Temperature – °F

Floating point register (1 of 2)

Read Only

41030

Return Temperature – °F

Floating point register (2 of 2)

Read Only

41031

Supply Temperature – °C

Floating point register (1 of 2)

Read Only

41032

Supply Temperature – °C

Floating point register (2 of 2)

Read Only

41033

Return Temperature – °C

Floating point register (1 of 2)

Read Only

41034

Return Temperature – °C

Floating point register (2 of 2)

Read Only

41075

Generic Rate Ai3

Floating point register (1 of 2)

Read Only

There are no engineering

units associated with

these registers.

41076

Generic Rate Ai3

Floating point register (2 of 2)

Read Only

41077

Generic Rate Ai4

Floating point register (1 of 2)

Read Only

41078

Generic Rate Ai4

Floating point register (2 of 2)

Read Only

Register

Address

Description

Register

Range

Data

Range

Over

Range

Read/Write

Comment

41001

Meter Operating Mode

Indicator

1 – 3

Not

applicable

Read Only

1 – indicates single mode

2 – indicates dual mode

3 – indicates bi-directional

mode

41002

Mode Status Indicator

1 – 2

Not

applicable

Read Only

1 - indicates heating mode

or forward direction

2 - indicates cooling mode

or reverse direction

Advertising