D-100 Dual Network Interface Installation Guide 07/14 - 1015

Page 22

Register

Address

Description

Register Type

Read/Write

Comment

41047

Volume Total Mode 1 –Gal

Floating point register (1 of 2)

Read Only

41048

Volume Total Mode 1 –Gal

Floating point register (2 of 2)

Read Only

41049

Volume Total Mode 2 –Gal

Floating point register (1 of 2)

Read Only

41050

Volume Total Mode 2 –Gal

Floating point register (2 of 2)

Read Only

41051

Volume Total Mode 1 – Liters

Floating point register (1 of 2)

Read Only

41052

Volume Total Mode 1 – Liters

Floating point register (2 of 2)

Read Only

41053

Volume Total Mode 2 – Liters

Floating point register (1 of 2)

Read Only

41054

Volume Total Mode 2 – Liters

Floating point register (2 of 2)

Read Only

41055

Volume Total Mode 1 – M³

Floating point register (1 of 2)

Read Only

41056

Volume Total Mode 1 – M³

Floating point register (2 of 2)

Read Only

41057

Volume Total Mode 2 – M³

Floating point register (1 of 2)

Read Only

41058

Volume Total Mode 2 – M³

Floating point register (2 of 2)

Read Only

41079

Volume Total Mode 1 – Ft³

Floating point register (1 of 2)

Read Only

41080

Volume Total Mode 1 – Ft³

Floating point register (2 of 2)

Read Only

41081

Volume Total Mode 2 – Ft³

Floating point register (1 of 2)

Read Only

41082

Volume Total Mode 2 – Ft³

Floating point register (2 of 2)

Read Only

41059

Mass Total –Lbs

Floating point register (1 of 2)

Read Only

Mass units are only

available when using

F-2000 Vortex Meter.

41060

Mass Total –Lbs

Floating point register (2 of 2)

Read Only

41061

Mass Total –kg

Floating point register (1 of 2)

Read Only

41062

Mass Total –kg

Floating point register (2 of 2)

Read Only

41063

Auxiliary Input Total (Di3)

Floating point register (1 of 2)

Read Only

41064

Auxiliary Input Total (Di3)

Floating point register (2 of 2)

Read Only

41066

Zero (+) Mode 1 Volume Total

0 – 1

0 – 1

Not

applicable

Read/Write

Write a value of 1 to

registers to reset totals.

Re-write a value of zero

to the register once the

totals reset.

41068

Zero (-) Mode 2 Volume Total

0 – 1

0 – 1

Not

applicable

Read/Write

41069

Zero Auxiliary Input Total (Di3)

0 – 1

0 – 1

Not

applicable

Read/Write

41070

Reserved for future use