ONICON D-100 Dualnet User Manual

Page 24

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

D-100 Dual Network Interface Installation Guide 07/14 - 1015

Page 24

Register

Address

Description

Register

Range

Data

Range

Over

Range

Read/Write

Comment

40042

Volume Total Mode 1 - kGal

0 – 65535 0 – 999

Read Only

Low Order

40043

Volume Total Mode 1 - MGal

0 – 65535 0 – 999

Read Only

Middle Order

40044

Volume Total Mode 1 – GGal

0 – 65535 0 – 65534

65535

Read Only

High Order

40045

Volume Total Mode 2 – kGal

0 – 65535 0 – 999

Read Only

Low Order

40046

Volume Total Mode 2 – MGal

0 – 65535 0 – 999

Read Only

Middle Order

40047

Volume Total Mode 2 – GGal

0 – 65535 0 – 65534

65535

Read Only

High Order

40048

Volume Total Mode 1 – kLiters 0 – 65535 0 – 999

Read Only

Low Order

40049

Volume Total Mode 1

MLiters 0 – 65535 0 – 999

Read Only

Middle Order

40050

Volume Total Mode 1 – GLiters 0 – 65535 0 – 65534

65535

Read Only

High Order

40051

Volume Total Mode 2 – kLiters 0 – 65535 0 – 999

Read Only

Low Order

40052

Volume Total Mode 2

MLiters 0 – 65535 0 – 999

Read Only

Middle Order

40053

Volume Total Mode 2 – GLiters 0 – 65535 0 – 65534

65535

Read Only

High Order

40054

Volume Total Mode 1 –M³

0 – 65535 0 – 999

Read Only

Low Order

40055

Volume Total Mode 1 – kM³

0 – 65535 0 – 65534

65535

Read Only

High Order

40056

Volume Total Mode 2 –M³

0 – 65535 0 – 999

Read Only

Low Order

40057

Volume Total Mode 2 – kM³

0 – 65535 0 – 65534

65535

Read Only

High Order

40058

Mass Total – kLbs

0 – 65535 0 – 999

Read Only

Mass units are only

available when using

F-2200 Vortex Meter.

40059

Mass Total – MLbs

0 – 65535 0 – 65534

65535

Read Only

40060

Mass Total – Kkgs

0 – 65535 0 – 999

Read Only

40061

Mass Total – Mkgs

0 – 65535 0 – 65534

65535

Read Only

40062

Auxiliary Input Total (Di3)

0 – 65535 0 – 999

Read Only

Low Order

40063

Auxiliary Input Total (x1000)

0 – 65535 0 – 65534

65535

Read Only

High Order

40065

Zero (+) Mode 1 Volume Total

0 – 1

0 – 1

Not

applicable

Read/Write

Write a value of 1 to

registers to reset totals.

Re-write a value of zero

to registers once the

totals reset.

40067

Zero (-) Mode 2 Volume Total

0 – 1

0 – 1

Not

applicable

Read/Write

40068

Zero Auxiliary Input Total (Di3)

0 – 1

0 – 1

Not

applicable

Read/Write