D-100 Dual Network Interface Installation Guide 07/14 - 1015

Page 25

3.3 TOTALIZATION, RESETTING TOTALS, OVER-RANGE & ROLLOVER

1. Integer Register Totalization

Holding registers 40026 through 40061 are integer registers that provide

totalized, volume and mass flow data in a variety of engineering units.

The registers are organized into pairs or groups of 3.

The first (low order) register is limited to a range of 0 – 999. This register rolls

over to zero when the total value reaches 1,000. If the registers are in a group

of 3, the second register (middle order) is also limited to a range of 0 – 999.

This register also rolls over when the register value reaches 1,000.

The second, or in the case of groups of 3, third, (high order) register is scaled

such that the smallest incremental value indicated is 1,000 times greater than

the preceeding register. An example of this is shown below.

Example - A group of 3 registers

Register

Engineering Units & Scaling

Current Value

40042

kGal (Gallons x 1,000)

00500

40043

MGal (Gallons x 1,000,000)

00015

40044

GGal (Gallons x 1,000,000,000)

00111

Low order + middle order + high order = Gallons Total = 111,015,500,000

or

kGal Total = 111,015,500

Registers 40062 and 40063 provide totalization for the optional auxiliary pulse input

option of the D-100. There are no engineering units associated with these registers.