OnLine Power Signal Saver IPC User Manual

Page 69

Advertising
background image


6002-1842 Rev A ECO# 8881

59

2.3.6.2 Unit

Specifications:


Menu 1 below (Figure 33) lists the BBS2000’s specifications.

Procedure: At the main menu, type 1 and press Enter. The screen displays the unit specifications as

shown below. To return to the main menu, press Enter.

Unit Model

BBS2000

The model name

[1-Unit Specifications ]

Unit Freq

60 hertz

Nominal operating frequency

Input Voltage

120 Volts

Nominal Input voltage

Output Voltage

120 Volts

Nominal output voltage

Output VA

2000 VA

The output VA capacity

Battery Voltage

48 Volts

Nominal battery voltage

Max Charge
Current

10 amps

MAX charge capacity

EEPROM Version

4.1

EEPROM version of the BBS2000

Figure 33

Unit Specifications Menu

2.3.6.3

Input / Output Values
Menu 2 below (Figure 34) lists the actual measurements of various input / output parameters.

Procedure: At the main menu, type 2 and press Enter. The screen displays the unit
specifications as shown below. To return to the main menu, press Enter.

Figure 34

Input/Output Values Menu

{2-INPUT/OUTPUT VALUES}

INPUT:

Voltage

120 Volts

The Input voltage

Freq.

60.1 Hertz

The Input frequency

OUTPUT:

Voltage

120 Volts

The Output voltage

Freq

60.1 Hertz

The Output frequency

Power

0000 Watts

The Output Power in Watts

BATTERY:

Temperature 25

°C

The ambient temperature of the battery case as read via
attached temperature probe

Voltage

53.8

The Battery DC voltage

Evt/Timer
Inv Event

00012

The Number of Input Power Failure

Evt Timer

13 Hours 36 Minutes

Total time that the battery was Discharged since
the last RESET

Advertising