6002-1842 Rev A ECO# 8881

60

2.3.6.4

Maintenance


Menu 3 below (Figure 35) lists the various maintenance options.

Procedure:

At the main menu, type 3 and press ENTER. The Maintenance Menu shown below is displayed. To return
to the main menu, press ENTER.

3-MAINTENANCE }

30 Battery Test Options


The start - stop for the Battery Test / Self Test is initiated here. The test duration
is user programmable in 1 minute intervals from 1 to 255 minutes. The factory
default setting is 1 minute.

Tip: The time duration can be changed only in the line mode.

[3 – Maintenance]

31 OUTPUT SHUTDOWN

This allows output to be switched OFF or Shutdown. BBS switches to STANDBY
mode when this option is activated.

32 INVERTER ON/OFF


During ON BATTERY or STANDBY mode, this option allows the inverter to
switch OFF or turn ON after the user programmable delay time.

The delay can be user programmable in 0.5 second steps from 0 to a maximum
setting of 255 steps (128 seconds). The delay is only available in Standby or
Battery modes. When the unit returns to line mode, the delay resets to a default
of 0 seconds.

During a battery discharge or ON BATTERY mode, the operator can stop the
inverter immediately after the user programmable delay time of 0 seconds to a
maximum of 300 seconds, prior to making the intersection dark.

33 CHANGE
PASSWORD*

This option allows for the change of password. The factory set default password
is 1111.

Tip: Password can only be changed in line mode.

34 LINE QUALIFY TIME

When input power returns and it is qualified, i.e., it is within the acceptable range,
the retransfer from Battery mode to Line mode is delayed by user programmed 3
/ 10 / 30 seconds to insure the line AC is stable and prevent unit cycling. The
factory set default value is 30 seconds.

35 BATTERY VOLTAGE
LEVEL % Capacity
Remaining


The level for LOW BATTERY ALARM as well as the activation of Normally Open
relay contact on com port connector is set here.

The Voltage level is user programmable in 0.5VDC increments from 42VDC to 55
VDC. The factory default setting is 47.5VDC or 40%. The relationship between
remaining % capacity of the battery and its DC Voltage depends on the
characteristics of the batteries used.

36 Load Shed Timer
ON/OFF (available in
Battery Mode only)

The programmable Timer contacts are manually activated / deactivated ON
DEMAND using this option. Certain Loads / Signals connected to this Timer can
be shed or dropped earlier to extend the back-up time.

This function is available only in “Battery Mode”.

Figure 35

Maintenance Menu (continued next page)