3 sound pressure level – REMKO RVT 263 DC User Manual

Page 11

Advertising
background image

2.3 Sound pressure level

1m

1m

5m

10m

1m

5m

10m

Fig. 3: Distance-dependent sound pressure level for the outdoor unit in relation to installation type, in accord-

ance with the drawing

Distance-dependent sound pressure level *)

Unit type

Sound power max.

[dB(A)]

Installation type, in

accordance with the

drawing

1m

[dB(A)]

5m

[dB(A)]

10m

[dB(A)]

15m

[dB(A)]

RVT 263 DC

59

In free field

51,0

37,0

31,0

27,5

In front of a wall

54,0

40,0

34,0

30,5

RVT 353 DC

63

In free field

55,0

41,0

35,0

31,5

In front of a wall

58,0

44,0

38,0

34,5

RVT 523 DC

61

In free field

53,0

39,0

33,0

29,5

In front of a wall

56,0

42,0

36,0

32,5

RVT 683 DC

67

In free field

59,0

45,0

39,0

35,5

In front of a wall

62,0

48,0

42,0

38,5

*) All information without guarantee. Exact sound values must be determined by an expert!

11