5.7 Oil return measures

If the outdoor unit is installed at a higher level than

the indoor unit, suitable oil return measures must

be taken. Usually, an oil pump bend is installed for

every 5.0 metres of height difference.

2

1

A

B

3

Fig. 34: Oil return measures

A: Outdoor unit

B: Indoor unit

1: One oil pump bend in suction pipe to outdoor

unit every 5.0 metres of height difference

2: Radius: 50 mm

3: Max. 10 m

5.8 Connection variants for the indoor unit

The following connection variants can be used for the refrigerant, condensate and control lines.

A

D

C

B

1

2

Fig. 35: Connection variants

A: Outlet on the wall, right

B: Outlet through the wall, right

C: Outlet through the wall, left

D: Outlet on the wall, left

1: Unit-side refrigerant piping (bendable)

2: Unit-side condensate drainage hose