5.5 Installation, mounting

outdoor unit

Outdoor unit installation location

n

The device may be attached only to a load-

bearing structure or wall. Ensure that the out-

door unit is installed only vertically. The instal-

lation site should be well ventilated.

n

To minimise noise, install floor consoles with

vibration dampers and a considerable distance

from acoustically-reflective walls to minimise

noise.

n

The minimum clearances specified on the next

page should be maintained when carrying out

the installation. These minimum distances

serve to ensure unrestricted air intake and

exhaust. Additionally, there must be adequate

space available for installation, maintenance

and repair.

n

If the outdoor unit is erected in an area of

strong winds, then the device must be pro-

tected against them (Fig. 31). The snow line is

to be observed during installation (Fig. 32).

n

The outdoor unit must always be installed on

vibration dampers. Vibration dampers prevent

the transmission of vibrations through the floor

or walls.

n

A heated, condensate tra ensures that conden-

sation from the pan can drain off. Ensure that

the condensate is prevented from freezing so

that it can drain off (gravel, drainage). The

Water Ecology Act is to be observed.

n

During installation, add about 20 cm to the

expected snow depth to guarantee unimpeded

intake and exhaust of outdoor air year round

(Fig. 32).

n

The installation site of the outdoor unit should

be agreed together with the operator primarily

so that operating noise is minimised and not in

terms of “short routes”. Thanks to the split-

design technology there are a great deal of dif-

ferent installation options with almost identical

efficiency available.

1

Fig. 31: Protection from wind

1: Wind

NOTICE!

The site for the outdoor unit must be selected

so that machinery noise that occurs disturbs

neither the residents nor the facility operator.

Observe the TA-noise specifications as well as

the table containing the drawings relating to

sound pressure levels..

20 cm

1

Fig. 32: Protection from snow

1: Snow

REMKO RVT...DC

28