8 electrical wiring, 1 general information, 2 connecting the indoor unit – REMKO RVT 263 DC User Manual

Page 39: 8electrical wiring

Advertising
background image

8

Electrical wiring

8.1 General Information

A protected power supply cable is to be connected

to the outdoor unit and a 4-wire control line to the

indoor unit respectively.

DANGER!

All electrical installation work is to be per-

formed by specialist companies. Disconnect

the power supply when connecting the elec-

trical terminals.

WARNING!

All electric lines are in accordance VDE regula-

tions to dimension and to lay.

NOTICE!

The electrical connection for the units must be

made at a separate feedpoint with a residual

current device in accordance with local regula-

tions and should be laid out by an electrician.

We recommend using shielded wires for the

control lines.

Check all plugged and clamped terminals to

verify that they are seated correctly and make

permanent contact. Tighten as required.

8.2 Connecting the indoor unit

n

We recommend installing a main / repair switch

on the building close to the indoor unit. This is

the responsibility of the customer.

n

The terminal blocks for making the connections

are located at the rear of the unit. When the

unit is installed, measurements can be made

from the front by removing the cover.

n

If an optional condensate pump is used in con-

junction with the unit, it may be necessary to

install an additional relay with a higher contact

rating after the switch-off contact on the pump

to switch off the compressor.

Make the connection as follows:

1.

Open the air inlet grill.

2.

Remove the covers on the right-hand side

(Fig. 46).

3.

Connect the customer-laid control line to the

terminals (Fig. 46).

4.

Re-assemble the unit.

2

1

4

3

1

Fig. 46: Connecting the indoor unit

1: Cover

2: Strain relief

3: Terminal block for control line

4: Control line from outdoor unit

39

Advertising
This manual is related to the following products: