23.0)

TROUBLESHOOTING GUIDE


T

urn on line volt

age

and thermost

at. Does

the green monitoring light come on in the junction box?

Y

es

No

Is there 120V between the L1 and L2 terminals on the terminal block in the junction box?

Y

es

No

Are the black lead wires of the green light securely on the terminals?

No

Y

es

Replace the green light.

Rep

air connection.

Check line volt

age at

thermost

at and line

volt

age curcuit. Rep

air

fault.

Is the draf

t inducer

on?

Y

es

No

Are the lead wires of the draf

t inducer

securely on the terminals L1 and L2 in the junction box?

No

Y

es

Rep

air connection.

Is 120V on one of the terminals of the lead wires of the draf

t

inducer motor?

Does the red monitoring light come on in the control cabinet?

Y

es

No

Is there 24 vac between terminals of the transformer on the secondary side in the junction box?

Y

es

No

Check the terminal block for continuity; replace it if no continuity

.

Rep

air connections.

Is the air hose securely connected to the air switch and the air sensing tubing at the draf

t inducer?

No

Clean out hose and probe.

T

roubleshooting

continued on the next page.

No

Y

es

Check terminal block for continuity

. Replace

it if no continuity

.

Disconnect the power and check motor lead wires.

Any wire

broken?

Y

es

No

Rep

air broken wires.

Check the blower wheel. Does it turn freely?

Y

es

Replace motor

Check blower wheel. Is there any damage?

Replace blower wheel.

Readjust blower wheel on shaf

t &

retighten set crew

.

Check the air sensing tube and hose.

Are

they clear and unobstructed?

Check the pressure at the air switch. Is it higher than the minimum required?

Is the red wire from transformer securely connected to air switch terminal C?

Move the red wire to air switch terminal C.

See the p

age af

ter

next for troubleshooting sequence.

Is the fuse OK in the junction box?

No

Y

es

Replace transformer

.

Are the black and white wires to the transformer securely on the terminals?

No

Y

es

Rep

air connection.

No

No

Y

es

No

No

Check the volt

age

between air switch terminal C and ground, is it 24 vac?

Y

es

Is there120 vac on the primary side of the transformer?

Y

es

No

When the draf

t

inducer is running, is there 24 vac between air switch terminal NO and ground ?

No

Replace the fuse.

Is one red wire connecting the transformer and one terminal of the fuse in the junction box?

No

Y

es

Correct connection.

Y

es

Y

es

No

Y

es

Y

es

Check the red wire from transformer for continuity

.

Replace it if no continuity

.

Y

es

Replace the air switch.

No

Check the air int

ake

and vent.

Are there

any blockages?

Y

es

No

Remove blockage. Rest

art

troubleshooting.

Check vent and fresh air lengths.

Are they

within the maximum permissible?

No

Y

es

Reduce them within the maximum permissible.

Remove the blower

.

Is the wheel free from dirt and dust?

Clean the blower wheel. Rest

art

troubleshooting.

No

Y

es

Does the blower turn freely?

No

Y

es

Replace the draf

t

inducer assembly

.

Check the restrictor plate st

amped ID. Is

it correct for the heater?

No

Y

es

Replace the restrictor plate.

Cont

act factory for

assist

ance.

No

Y

es

Correct connection.

Is another red wire connecting the air switch terminal C and the other terminal of the fuse in the junction box?