Super Systems 7EK 31080 User Manual

Page 14

Advertising
background image

10

13 = mA

Linear

range

0 /

20 mA

14 = mA

Linear

range

4 /

20 mA

15 = V

Linear

range

0 /

5 V

16 = V

Linear

range

1 /

5 V

17 = V

Linear

range

0 /

10 V

18 = V

Linear

range

2 /

10 V

19 = TC type

L

range

0 /

+1650 °F

20 = TC type

J

range

-150 /

+1830 °F

21 = TC type

K

range

-150 /

+2500 °F

22 = TC type

N

range

-150 /

+2550 °F

23 = TC type

R

range

0 /

+3200 °F

24 = TC type

S

range

0 /

+3200 °F

25 = RTD type

Pt 100

range

-199.9 /

+400.0 °F

26 = RTD type

Pt 100

range

-330 /

+1470 °F

27 = TC type

T

range

-199.9 /

400.0 °C

28 = TC type

T

range

-330 /

750 °F

NOTE: selecting P1 = 0, 2, 4, 9, 25 or 27, the instrument
set automatically P40 = FLtr. For all the remaining ranges
it will set P40 = nOFL.

P2 = Decimal point position
This parameter is available only when a linear input is
selected (P1 = 11 to 18).

----.

= No decimal figure.

---.-

= One decimal figure.

--.--

= Two decimal figures.

-.---

= Three decimal figures.

P3 = Initial scale value
For linear inputs it is programmable from -1999 to 4000.
For TC and RTD input it is programmable within the input
range.
Notes:
1) When this parameter is modified, rL parameter will be

re-aligned to it.

2) If a linear input is selected, the value of this parameter

can be greater than P4 in order to get a reverse
readout.

P4 = Full scale value
For linear inputs it is programmable from -1999 to 4000.
For TC and RTD inputs, it is programmable within the
input range.

Notes:
1) When this parameter is modified, rH parameter will be

re-aligned to it.

2) If a linear input is selected, the value of this parameter

can be smaller than P3 in order to get a reverse
readout.

The initial and full scale values determine the input span
which is used by the PID algorithm, the SMART and the
alarm functions.

NOTE: the minimum input span (S = P4 - P3), in absolute
value, should be set as follows:
- For linear inputs, S > 100 units.
- For TC input with °C readout, S > 300 °C.
- For TC input with °F readout, S > 550 °F.
- For RTD input with °C readout, S > 100 °C.
- For RTD input with °F readout, S > 200 °F.

P5 = Output 1 type
Changing the P5 setting, also Cy1 parameter will be
automatically modified.
rEL = Relay [the cycle time (Cy1) will be forced to

15 s]

SSr = SSR [the cycle time (Cy1) will be forced to 4 s]

P6 = Output 1 action
This parameter is skipped if P7 = 4
rEV = Reverse action (Heating action)
dir = Direct action (Cooling action)

t

INPUT

t

OUTPUT

t

INPUT

t

OUTPUT

Reverse

Direct

31080-1-00.p65

3/24/00, 11:58 AM

10