Super Systems 7EK 31080 User Manual

Page 6

Advertising
background image

2

LINEAR INPUT

Fig. 4 mA, mV AND V INPUTS WIRING

NOTES:
1) Don’t run input wires together with power cables.
2) Pay attention to the line resistance; a high line

resistance may cause measurement errors.

3) When shielded cable is used, it should be grounded at

one side only to avoid ground loop currents.

RTD INPUT

Fig. 3 RTD INPUT WIRING

Input: for RTD Pt 100

W

, 3-wire connection.

Line resistance: automatic compensation up to 20

W

/wire

with no measurable error.

NOTES:
1) Don’t run input wires together with power cables.
2) Pay attention to the line resistance; a high line

resistance may cause measurement errors.

3) When shielded cable is used, it should be grounded at

one side only to avoid ground loop currents.

4) The resistance of the 3 wires must be the same.

4

RTD

1

3

4

RTD

1

3

mA,

mV

or

V

3

Shield

1

3

1

G

_

+

_

+

mA,

mV

or

V

Input type

11
12
13
14
15
16
17
18

0 - 60 mV

12 - 60 mV

0 - 20 mA
4 - 20 mA

0 - 5 V
1 - 5 V
0 - 10 V
2 - 10 V

impedance

> 1 M

W

< 5

W

> 200 k

W

> 400 k

W

Accuracy

0.2 % + 1 digit

@ 25°C