Super Systems 7EK 31080 User Manual

Page 15

Advertising
background image

11

P7 = Output 2 function.
0 =

output not used.

1 =

it is used as Alarm 1 output and the alarm 1 is
programmed as process alarm.

2 =

it is used as Alarm 1 output and the alarm 1 is
programmed as band alarm.

3 =

it is used as Alarm 1 output and the alarm 1 is
programmed as deviation alarm.

4 =

it is used as secondary control output (Cooling
output).

NOTE: setting P7 = 4, the P6 parameter is forced to "rEV".

P8 = Cooling media.
Available only when P7 = 4
- AIr = Air is used as cooling media.
- OIL = Oil is used as cooling media.
- H2O = Direct water is used as cooling media.
Changing P8 parameter, the instrument forces the cycle
time and relative cooling gain parameter to the default
value related with the chosen cooling media
When

P8 = AIr

- Cy2 = 10 s and rC = 1.00

P8 = OIL

- Cy2 = 4 s and rC = 0.80

P8 = H2O

- Cy2 = 2 and rC = 0.40

P9 = Alarm 1 operating mode
Available only when P7 is equal to 1,2 or 3.
H.A. = High alarm (outside for band alarm) with

automatic reset.

L.A. =

Low alarm (inside for band alarm) with automatic
reset.

H.L. =

High alarm (outside for band alarm) with manual
reset (latched alarm).

L.L. =

low alarm (inside for band alarm) with manual
reset (latched alarm).

P10 = Current measurement (in Amp.)
(See also "Display function" and "Out 1 failure detection").
OFF = Current measurement disabled
n.O. =

Set P10 to n.O. when the load is energized during
the ON status of the instrument output (relay ener-
gized or SSR output status 1).

n.C. =

Set P10 to n.C. when the load is energized during
the OFF status of the instrument output (relay de-
energized or SSR output status 0).

P11 = Current transformer range
This parameter is present only if P10 is different from OFF.
Programmable from 10 to 100 A.

P12 = Output 3 function
0 =

Output not used for alarm 2.

1 =

it is used as Alarm 2 output and the alarm 2 is
programmed as process alarm.

2 =

it is used as Alarm 2 output and the alarm 2 is
programmed as band alarm.

3 =

it is used as Alarm 2 output and the alarm 2 is
programmed as deviation alarm.

NOTE: The output 3 relay operates as a logic OR among
the alarm 2, the "Out 1 failure detection" (OFD) function
and the "Loop break alarm" (LBA) function.

P13 =

Alarm 2 operating mode & type of reset
assigned to "Output 1 failure detection" and
"Loop Break Alarm" functions.

Available only when P12 is different from 0 or P10 is
different from OFF or P47 is different from dIS.
H.A. = High alarm (outside for band alarm) with

automatic reset.

L.A. =

Low alarm (inside for band alarm) with automatic
reset.

H.L. =

High alarm (outside band) with manual reset
(latched alarm).

L.L. =

low alarm (inside band) with manual reset
(latched alarm).

NOTE: The "Out 1 failure detection" and "loop break
alarm" functions assume only the selected reset type
(manual or automatic).

P14 = Output 4 function
0 =

Output not used.

1 =

it is used as Alarm 3 output and the alarm 3 is
programmed as process alarm.

2 =

it is used as Alarm 3 output and the alarm 3 is
programmed as band alarm.

3 =

it is used as Alarm 3 output and the alarm 3 is
programmed as deviation alarm.

31080-1-00.p65

3/24/00, 11:58 AM

11