1

MOUNTING REQUIREMENTS

These instruments are intended for permanent
installation, for indoor use only, in an electrical panel
which encloses the rear housing, exposed terminals and
wiring on the back.
Select a mounting location where the instrument is subject
to minimum vibration and the ambient temperature range
is between 0 and 50 °C.
These instruments can be mounted on a panel up to 15
mm thick with a square cutout of 45 x 92 mm .
For outline and cutout dimensions refer to Fig. 2.
The surface texture of the panel must be better than
6,3

m

m.

The instrument is shipped with rubber panel gasket.
To assure the IP65 and NEMA 4 protection, insert the
panel gasket between the instrument and the panel as
shown in fig. 1.
While holding the instrument against the panel proceed as
follows:
1) insert the gasket in the instrument case;
2) insert the instrument in the panel cutout;
3) pushing the instrument against the panel, insert the

mounting bracket;

4) with a screwdriver, turn the screws with a torque

between 0.3 and 0.4 Nm.

CONNECTIONS

A) MEASURING INPUTS
NOTE
: Any external component (like zener barriers etc.)
connected between sensor and input terminals may cause
errors in measurement due to excessive and/or not
balanced line resistance or possible leakage currents.

TC INPUT

Fig. 2 THERMOCOUPLE INPUT WIRING

External resistance: 100

W

max, maximum error 0.1% of

span.
Cold junction: automatic compensation from 0 to 50 °C.
Cold junction accuracy: 0.1 °C/°C
Input impedance: > 1 M

W

NOTES:
1)

Don’t run input wires together with power cables.

2)

For TC wiring use proper compensating cable
preferable shielded.

3)

when a shielded cable is used, it should be connected
at one point only.

3

+

_

Shield

1

3

+

_

Shield

1

panel

screw

Fig. 1

bracket

gasket

screw

bracket

31080-1-00.p65

3/24/00, 11:58 AM