Super Systems 7EK 31080 User Manual

Page 29

Advertising
background image

Appendix A.1

APPENDIX A
DEFAULT PARAMETERS

DEFAULT RUN TIME PARAMETERS

PARAMETER

DEFAULT VALUE

SP

= Initial scale value

SnRT

= Disable

n.SRt

= OFF

SP2

= Initial scale value

nnn

= OFF

AL1

= Initial scale value for process alarm

0 for deviation or band alarm

HSA1

= 0.1 %

AL2

= Initial scale value for process alarm

0 for deviation or band alarm

HSA2

= 0.1 %

AL3

= Initial scale value for process alarm
= 0 for deviation or band alarm

HSA3

= 0.1 %

PB

= 4.0 %

HyS

= 0.5 %

ti

= 4.00 (4 minutes)

td

= 1.00 (1 minute)

IP

= 30 % if one control output is

configured

= 0 if two control outputs are

configured

Cy1

= 15 seconds for relay output
= 4 seconds for SSR output

Cy2

= 10 seconds for P8 = AIr
= 4 seconds for P8 = OIL
= 2 seconds for P8 = H2O

rC

= 1.00 for P8 = AIr
= 0.80 for P8 = OIL
= 0.40 for P8 = H2O

OLAP

= 0

rL

= Initial scale value

rH

= Full scale value

Grd 1

= Infinite (step transfer)

Grd 2

= Infinite (step transfer)

OLH

= 100 %

tOL

= Infinite

Hbd

= 50 % of the full scale value

SCA

= 100% of the full scale value

rnP

= Infinite

31080-A-00.p65

3/24/00, 11:58 AM

1

Advertising