NOTE: the minimum input span (S = P4 - P3), in absolute
value, should be set as follows:
- For linear inputs, S > 100 units.
- For TC input with °C readout, S > 300 °C.
- For TC input with °F readout, S > 550 °F.
- For RTD input with °C readout, S > 100 °C.
- For RTD input with °F readout, S > 200 °F.

P5 = Output 1 function
rEv

= Out 1 used as control output with reverse action
(heating).

dIr

= Out 1 used as control output with direct action
(cooling).

Pv.rt

= Out 1 retransmits the process variable.

SP.rt

= Out 1 retransmits the operative set point.

P6 = Output 1 type
0-20 = output 1 type 0 - 20 mA
4-20 = output 1 type 4 - 20 mA

P7 = Retransmission - Initial scale value
P7 is available only when P5 = Pv.rt or SP.rt.
Range: from -1999 to 4000.

P8 = Retransmission - Full scale value
P8 is available only when P5 = Pv.rt or SP.rt.
Range: from -1999 to 4000.

P9 = Output 2 function.
nonE

= output not used.

rEv

= Out 2 is used as control output with reverse

action (heating).

24 = TC type

N

range

-150 /

+2550 °F

25 = TC type

R

range

0 /

+3200 °F

26 = TC type

S

range

0 /

+3200 °F

27 = RTD type

Pt 100 range

-199.9 /

+400.0 °F

28 = RTD type

Pt 100 range

-330 /

+1470 °F

NOTE: selecting P1 = 0, 2, 4, 6, 10 or 27, the instrument
set automatically P44 = P45 = FLtr. For all the remaining
ranges it will set P44 = P45 = nOFL.

P2 = Decimal point position
This parameter is available only when a linear input is
selected (P1 = 12, 13, 14, 15, 16, 17, 18 or 19).

----.

= No decimal figure.

---.-

= One decimal figure.

--.--

= Two decimal figures.

-.---

= Three decimal figures.

P3 = Initial scale value
For linear inputs it is programmable from -1999 to 4000.
For TC and RTD input it is programmable within the input
range.
Notes:
1) When this parameter is modified, rL parameter will be

re-aligned to it.

2) If a linear input is selected, the value of this parameter

can be greater than P4 in order to get a reverse
readout.

P4 = Full scale value
For linear inputs it is programmable from -1999 to 4000.
For TC and RTD inputs, it is programmable within the
input range.
Notes:
1) When this parameter is modified, rH parameter will be

re-aligned to it.

2) If a linear input is selected, the value of this parameter

can be smaller than P3 in order to get a reverse
readout.

The initial and full scale values determine the input span
which is used by the PID algorithm, the SMART and the
alarm functions.

REVERSE ACTION

DIRECT ACTION

t

Input

t

Output

t

Input

t

Output