Super Systems 7EK 31081 User Manual

Page 31

Advertising
background image

Appendix A.1

APPENDIX A
DEFAULT PARAMETERS

DEFAULT OPERATIVE PARAMETERS
The control parameters can be loaded with predetermined
default values. These data are the typical values loaded in
the instrument prior to shipment from factory.

To load the default values proceed as follows:

a)

The SMART function should be disabled.

b)

The instrument is in "UNLOCK" condition.

c)

The upper display will show the process variable while
the lower display will show the set point value.

d)

Held down

t

pushbutton and press

s

pushbutton;

the display will show:

e)

Press

s

or

t

pushbutton; the display will show:

f) Press FUNC pushbutton; the display will show:

This means that the loading procedure has been initiated.
After about 3 seconds the loading procedure is terminated
and the instrument reverts to NORMAL DISPLAY mode.

The following is a list of the default operative parameters
loaded during the above procedure:

PARAMETER

DEFAULT VALUE

SP

= Initial scale value

SñRT

= Disable

ñ.SRt

= OFF

SP2

= Initial scale value

SP3

= Initial scale value

SP4

= Initial scale value

nnn

= OFF

AL1

= Initial scale value for process alarm

0 for deviation or band alarm

HSA1

= 0.1 %

AL2

= Initial scale value for process alarm

0 for deviation or band alarm

HSA2

= 0.1 %

AL3

= Initial scale value for process alarm
= 0 for deviation or band alarm

HSA3

= 0.1 %

PB

= 4.0 %

HyS

= 0.5 %

ti

= 4.00 (4 minutes)

td

= 1.00 (1 minute)

IP

= 30 % if one control output is

configured

= 0 if two control outputs are

configured

Cy2

= 15 seconds for relay output

4 seconds for SSR output
When two control output are
programmed and OUT 2 = "dir" the
default value will be:
10 seconds for P25 = AIr
4 seconds for P25 = OIL
2 seconds for P25 = H2O

Cy3

= 15 seconds for relay output

When two control output are
programmed and OUT 3 = "dir" the
default value will be:
10 seconds for P25 = AIr
4 seconds for P25 = OIL
2 seconds for P25 = H2O

rC

= 1.00 for P25 = AIr
= 0.80 for P25 = OIL
= 0.40 for P25 = H2O

OLAP

= 0

rL

= Initial scale value

rH

= Full scale value

Grd 1

= Infinite (step transfer)

Grd 2

= Infinite (step transfer)

OLH

= 100 %

tOL

= Infinite

rñP

= Infinite

31081-A-00.p65

3/24/00, 11:59 AM

1