Super Systems 7EK 31081 User Manual

Page 20

Advertising
background image

15

P38 =

Minimum value of the integral time calculated
by the SMART algorithm.

This parameter is skipped when no one of the output is
configured as control output or P35 =0.
It is programmable from 00.01[mm.ss] to 02.00 [mm.ss].

P39 = MANUAL function
This parameter is skipped when no one of the output is
configured as control output.

OFF = manual function is disabled
On =

manual function can be enabled/disabled by
MAN pushbutton or serial link.

P40 =

Device status at instrument start up.

This parameter is skipped when no one of the output is
configured as control output or P39 =OFF.
0 =

The instrument starts in AUTO mode.

1 =

It starts in manual mode with power output =0

2 =

It starts in the same way it was prior to the power
shut down (if in manual mode the power output is set
to zero).

3 =

It starts in the same way it was prior to the power
shut down (if in manual mode the power output will
be the last value prior to power shut down).

P41 = Timeout selection
This parameter allows to set the time duration of the
timeout for parameter setting used by the instrument
during the operating mode.
tn. 10 = 10 seconds
tn. 30 = 30 seconds

P42 = Conditions for output safety value
This parameter is skipped when no one of the output is
configured as control output.
0 = No safety value (see "Error Messages" chapter)
1 =

Safety value applied when overrange or underrange
condition is detected.

2 =

Safety value applied when overrange condition is
detected.

3 =

Safety value applied when underrange condition is
detected.

-

For readout ranges without decimal figure, P33 is
programmable from -199 to 199.

P34 = Displayable protected parameters
This parameter is skipped when P20 = 0.

OFF = Protected parameters cannot be displayed.
On =

Protected parameter can be displayed.

P35= SMART function
This parameter is skipped when no one of the output is
configured as control output.
0 =

SMART function disabled.

1 =

The SMART enable/disable is NOT protected by safety
lock.

2 =

The SMART enable/disable is under safety lock protec-
tion.

P36 =

Maximum value of the proportional band
calculated by the SMART algorithm.

This parameter is skipped when no one of the output is
configured as control output or P35 =0.
This parameter is programmable from P37 value to
200.0 %.

P37 =

Minimum value of the proportional band
calculated by the SMART algorithm.

This parameter is skipped when no one of the output is
configured as control output or P35 =0.
It is programmable from 1.0% to P36 value.

Real curve

Readout

Adjusted
curve

Input

P33

31081-1-00.p65

3/24/00, 11:59 AM

15