Super Systems 7EK 31081 User Manual

Page 23

Advertising
background image

18

OPERATIVE MODE

DISPLAY FUNCTIONS
The upper display shows the measured values while the
lower display shows the programmed set point value (we
define the above condition as “normal display mode”).
Note: When the rate of change (Grd1, Grd2) is utilized,

the displayed set point value may be different
from the operating setpoint.

By pushing the FUNC key for more than 3 s but less than
10s. it is possible to change the information on the lower
display as follows:

r

.

followed by the power value of the output configured as
"rEv" (from 0.0 to 100.0%).
Push FUNC key again, the lower display will show:

d

.

followed by the power value of the output configured as
"dir" (from 0.0 to 100.0%).
NOTE: the graphic symbol " . " means 100.0 %.
Push FUNC key again, the lower display will show:

U

.

followed by the firmware version.

Push FUNC pushbutton again. The display will return
in "Normal Display Mode".

NOTE: The information will be displayed only if the relative
function has been previously configured.
When no pushbutton is pressed during the time out (see
P41), the display will automatically return in "Normal
Display Mode".
In order to keep the desired information continuously on

the lower display, depress

s

or

t

pushbuttons to

remove the timeout.
When is desired to return in "Normal Display Mode" push
FUNC pushbutton again.

SET POINTS
This instrument is provided of 4 set points (SP, SP2, SP3
and SP4).
By setting the P47 parameter it is possible to limit the
number of the available set points.
The set point selection is possible only by logic inputs 1
and 2 (terminals 6, 7 and 8).

Logic input 1

Logic input 2

Op. Set point

open (6 -7)

open (6 -8)

SP

open (6 -7)

closed (6 -8)

SP2

closed (6 -7)

open (6 -8)

SP3

closed (6 -7)

closed (6 -8)

SP4

INDICATORS
°C

Lit when the process variable is shown in
centigrade degree.

°F

Lit when the process variable is shown in
Fahrenheit degree.

SMRT

- Flashing when the first part of the SMART

algorithm is active.

- Lit when the second part of the SMART

algorithm is active.

OUT1

flashes with a duty cycle proportional to the OUT
1 power.

OUT2

Lit when OUT 2 is ON or alarm 1 is in the alarm
state.

OUT3

Lit when OUT 3 is ON or alarm 2 is in the alarm
state.

OUT4

- Lit when the alarm 3 is in alarm condition.
- Flashing with slow rate when loop break alarm

is in alarm condition

- Flashing with high rate when alarm 3 and loop

break alarm are in alarm condition.

REM

Lit when the instrument is in REMOTE condition
(functions and parameters are controlled via
serial link).

SPX

Lit when SP2, SP3 or SP4 are used.
Flashes when a set point from serial link is used.

MAN

Lit when the instrument is in MANUAL mode.

31081-1-00.p65

3/24/00, 11:59 AM