Super Systems 7EK 31081 User Manual

Page 8

Advertising
background image

3

TX INPUT

Fig. 5 TX INPUT WIRING
NOTES:
1) Don’t run input wires together with power cables.
2) When shielded cable is used, it should be grounded at

one side only and possibly to the terminal 6 of the
instrument.

3) The impedance of the 20 mA input, is less than 5

W

.

4) The auxiliary power supply (AUX) is rated:

24 V DC (+ 10%), 25 mA maximum.

5) The auxiliary power supply (AUX) is NOT isolated from

measuring input. A duble or reinforced isolation
between instrument input and power line must be
assured by the external transmitter.

B) LOGIC INPUT
Safety note:
1) Do not run logic input wiring together with power

cables.

2) Use an external dry contact capable to switch 0.5 mA,

5 V DC.

3) The instrument needs 100 ms to recognize a contact

status variation.

4) The logic inputs are NOT isolated by the measuring

input. A double or reinforced isolation between logic
inputs and power line must be assured by the external
elements.

Fig. 6 - LOGIC INPUT WIRING

This instrument is provided with 4 set points (SP, SP2,
SP3 and SP4).
The set point selection is possible only by logic inputs 1
and 2 (terminals 6, 7 and 8).

Logic input 1

Logic input 2

Op. Set point

open (6 - 7)

open (6 - 8)

SP

open (6 - 7)

closed (6 - 8)

SP2

closed (6 - 7)

open (6 - 8)

SP3

closed (6 - 7)

closed (6 - 8)

SP4

3

1

6

5

PWR

+

4-wire

transmitter

OUT

+

OUT

-

PWR

-

IN +

IN -

AUX +

AUX -

3

1

6

5

PWR

+

3-wire

transmitter

OUT

+

GND

IN +

IN -

AUX +

AUX -

3

1

6

5

2-wire

transmitter

OUT

-

OUT

+

IN +

IN -

AUX +

AUX -

8

Log. input 2

7

Log. input 1

6

31081-1-00.p65

3/24/00, 11:59 AM

3