Super Systems 7EK 31081 User Manual

Page 17

Advertising
background image

12

AL2.P = it is used as Alarm 2 output and the alarm 2 is

programmed as process alarm.

AL2.b = it is used as Alarm 2 output and the alarm 2 is

programmed as band alarm.

AL2.d =it is used as Alarm 2 output and the alarm 2 is

programmed as deviation alarm.

NOTE:
Setting P12 = rEv, the "out 3 cycle time" (Cy3) will be
forced to 15 seconds
Setting P12 = dir, the "out 3 cycle time" (Cy3) will be
forced to:

10 seconds when P25 = AIr
4 seconds when P25 = OIL
2 seconds when P25 = H2O

NOTES to P5, P9 and P12 relation.
1)

Only 1 of the 3 outputs can be configured as "rEv".

2)

Only 1 of the 3 outputs can be configured as "dir".

3)

When none of the 3 outputs is configured as control
output the instrument will operate as a standard
indicator.

P13 = Alarm 2 operating mode
Available only when P12 = AL2.P, AL2.b or AL2.d.
H.A. = High alarm (outside for band alarm) with

automatic reset.

L.A. =

Low alarm (inside for band alarm) with automatic
reset.

H.L. =

High alarm (outside for band alarm) with manual
reset(latched).

L.L. =

Low alarm (inside for band alarm) with manual
reset(latched).

P14 = Output 4 function
nonE

= output not used.

AL3.P = it is used as Alarm 3 output and the alarm 3 is

programmed as process alarm.

AL3.b = it is used as Alarm 3 output and the alarm 3 is

programmed as band alarm.

AL3.d =it is used as Alarm 3 output and the alarm 3 is

programmed as deviation alarm.

NOTE: The alarm 3 and the "Loop break alarm" are in OR
condition on the same output (OUT 4).

dir

= Out 2 is used as control output with direct

action (cooling).

AL1.P = it is used as Alarm 1 output and the alarm 1 is

programmed as process alarm.

AL1.b = it is used as Alarm 1 output and the alarm 1 is

programmed as band alarm.

AL1.d =it is used as Alarm 1 output and the alarm 1 is

programmed as deviation alarm.

NOTES:
Setting P9 = rEv, the "out 2cycle time" (Cy2) will be forced
to:

15 seconds when P10 = rEL
4 seconds when P10 = SSr

Setting P9 = dir, the "out 2cycle time" (Cy2) will be forced
to:

10 seconds when P25 = AIr
4 seconds when P25 = OIL
2 seconds when P25 = H2O

P10 = Output 2 type
This parameter is skipped when P9=nonE.
rEL = Relay

SSr = SSR

NOTES:
When P9=rEv and P10 = rEL, the "out 2cycle time" (Cy2)
will be forced to 15 seconds
When P9=rEv and P10 = SSr, the "out 2cycle time" (Cy2)
will be forced to 4 seconds

P11 = Alarm 1 operating mode
Available only when P9 = AL1.P, AL1,b or AL1.d.
H.A. = High alarm (outside for band alarm) with

automatic reset.

L.A. = Low alarm (inside for band alarm) with automatic

reset.

H.L. = High alarm (outside for band alarm) with manual

reset (latched).

L.L. = Low alarm (inside for band alarm) with manual

reset(latched).

P12 = Output 3 function
nonE

= output not used.

rEv

= Out 3 is used as control output with reverse

action (heating).

dir

= Out 3 is used as control output with direct

action (cooling).

31081-1-00.p65

3/24/00, 11:59 AM

12