9101 Connections

21

DC Power

To power the unit from a DC source, use part number 9-9100-028-1, shown in
Figure 2-3). Follow the procedures below to connect and disconnect the power
supply. The power connection procedure applies power to the unit.

Connecting the DC Power Supply

WARNING: Before completing any of the following steps and to prevent short-circuit
or shock hazards, ensure that power removed from the DC circuit. To ensure that all

power is Off, locate the circuit breaker on the panel board that services the DC circuit,
switch the circuit breaker to the Off position, and tape the switch handle of the circuit
breaker in the Off position.

WARNING: When installing the unit, the ground connection must always be made first
and disconnected last.

1

Ensure that power is removed from the 48 volt source as indicated in the first
warning above.

2

Connect the green/yellow chassis ground wire of the DC power supply to the
ground lug or screw of the 48 volt source.

3

Connect the black (+) wire of the DC power supply to the return screw of the 48
volt source.

4

Connect the white (

) wire of the DC power supply to the

48 volt screw of the

48 volt source.

5

Connect the DC power supply to the MultiPro unit.

6

Apply power to the circuit. This applies power to the MultiPro unit.

DC INPUT

20 to 60VDC

2.7A MAX

(BLK + )(WHT

- )

(GRN/YEL CHAS GND)

Black +

White -

Green/Yellow Chassis Ground