Vav system, Oe361 – commlink ii communications interface, Description – WattMaster MG331-21-VAVCAV User Manual

Page 14: Mounting

Advertising
background image

Form: WMS-OE361-CommLink-1B.doc

Page

1 of 1

VAV System

Description

The OE361 - CommLink II Communica-
tions Interface allows user access to any
controller connected to the controls sys-
tem. The CommLink II comes packaged
in an attractive beige colored plastic en-
closure. The CommLink II is powered by
a small wall mounted plug-in transformer
that is included. Locally, an optional on-
site computer may be connected to the
CommLink II for direct access to system
control parameters. Remote access is
obtained via an optional modem which is
connected with the CommLink II Com-
munication Interface. With a modem in-
stalled, the CommLink II may be config-
ured to call a number, if an alarm condi-
tion occurs. With the modem option the
system could be dialed and monitored
from a remote location by a PC. Com-
puter and modem cables (6ft long) are
provided with the CommLink II.

Mounting

If an on-site computer is to be used for
direct connection and monitoring of the
system, the CommLink II should be lo-
cated near the computer terminal to
monitor the system. If no on-site com-
puter is to be used, locate the CommLink
II near the phone line jack for ease of
connection to a modem. If for any reason
you use cables of greater length than
those provided with the CommLink II (6 ft.
long) be sure the cables that connect the
CommLink II to the modem and the
CommLink II to the on-site computer do
not exceed twenty-five feet in length.

Technical Data

OE 361 - CommLink II Communication Interface

Power

24 Volt AC

Computer Connection

RS-232

Plug-in Transformer

110V to 24V (Included)

Network Connection

RS-485

Power Consumption

14 VA Maximum

Protocol

HSI Open Protocol Token Passing

Operating Temperature

10

°

F to 140

°

F

Physical Connections

(2) 9 Pin/DB9 Male

Operating Humidity

90% RH Non-Condensing

Communications

RS-485 - 9600 Baud

Three Year Warranty

WattMaster reserves the right to change specifications without notice