Duct Temperature Sensor

1

JOB NAME

04/25/02

G-DUCSENS1.CDR

OE230 & OE231

Duct Temperature Sensors

OE230 (6" Probe) & OE231 (12" Probe)

Mounting Plate

Gasket

Adhesive Backed Drill Guide

Mounting Template

11-1/2" (OE231)

5-1/2" (OE230)

Mounting Plate

4.0"

3/4"

1/4" Hex Head Sheet Metal Screws

Thread

Together

Duct Work

Drill 5/16" Hole In Ductwork For Probe

Leads Are Non-polarized.

Butt Splice Leads To 24 Gauge

Wire Minimum. Connect Leads

To "Analog In" And "Ground"

At Controller.

Notes:

1.)All Wiring To Be In Accordance With

Local And National Electrical Codes

And Specifications.

Temperature Sensor Resistance/Voltage Chart

Temp

Resistance* Voltage

F

Ohms

@ Input*

-10.............93333........4.620

-5...............80531........4.550

0...............69822........4.474

5...............60552........4.390

10..............52500........4.297

15..............45902........4.200

20..............40147........4.095

25..............35165........3.982

30..............30805........3.862

35..............27140........3.737

40..............23874........3.605

°

Temp

Resistance* Voltage

F

Ohms

@ Input*

°

45..............21094........3.470

50..............18655........3.330

52..............17799........3.275

54..............16956........3.217

56..............16164........3.160

58..............15385........3.100

60..............14681........3.042

62..............14014........2.985

64..............13382........2.927

66..............12758........2.867

68..............12191........2.810

Temp

Resistance* Voltage

F

Ohms

@ Input*

°

69..............11906 ........2.780

70..............11652 ........2.752

71..............11379 ........2.722

72..............11136 ........2.695

73..............10878........2.665

74..............10625........2.635

75..............10398........2.607

76..............10158........2.570

78..............9711 ..........2.520

80..............9302..........2.465

82..............8893..........2.407

Temp

Resistance* Voltage

F

Ohms

@ Input*

84..............8514..........2.352

86..............8153..........2.297

88..............7805..........2.242

90..............7472..........2.187

95..............6716..........2.055

100............6047..........1.927

105............5453..........1.805

110 ............4923..........1.687

115 ............4449..........1.575

120............4030..........1.469

°

125............3656..........1.369

*Chart Notes:

1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).

2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts.

Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltage

is above 5.08 VDC, the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.

The Duct Sensor Is Used For Sensing Supply

Or Return Air Temperatures. Location Of The

Sensors Is Very Important In Order To Obtain

Accurate Temperature Readings. The

Following Recommendations Should Be

Followed:

When Used As A Supply Air Sensor The

Sensor Should Be Mounted In The Supply Air

Duct As Close To The HVAC Unit As Possible

And Upstream Of The Bypass Damper (If

Used) For Best Results. For Best Accuracy,

Apply Insulation On The Outside Of The

Ductwork Over The Sensor. This Will Help

Thermal Gradients From Affecting The Sensor.

Supply Air

Return Air

When Used As A Return Air Sensor The

Sensor Should Be Mounted In The Return Air

Duct As Close To The HVAC Unit As Possible

And Upstream Of The Bypass Damper (If

Used) For Best Results. For Best Accuracy,

Apply Insulation On The Outside Of The

Ductwork Over The Sensor. This Will Help

Thermal Gradients From Affecting The Sensor.

See The Systems Installation And Operation

Manual For Other Design Considerations And

Recommendations Regarding Duct

Temperature Sensor Location.