Outside air humidity sensor – WattMaster MG331-21-VAVCAV User Manual

Page 38

Advertising
background image

1.63"

Notes:

FILENAME

DATE:

B. CREWS

DESCRIPTION:

PAGE

DRAWN BY:

Outside Air Humidity Sensor

1

JOB NAME

4.)All Wiring To Be In Accordance With

Local And National Electrical Codes

And Specifications.

3.)Gasket Must Be Installed Under Cover

Plate To Provide Raintight Seal.

Rainwater Will Damage Sensor!

05/14/01

G-OA-HUMID1.CDR

OE265-03

Front View

Side View

Back View

Humidity Sensor Current/Voltage Chart

RH

Output*

Output

mA

VDC*

0...............4.00...........1.00

5...............4.80...........1.20

10..............5.60...........1.40

15..............6.40...........1.60

20..............7.20...........1.80

25..............8.00...........2.00

30..............8.80...........2.20

35..............9.60...........2.40

40..............10.40.........2.60

45..............11.20 .........2.80

50..............12.00.........3.00

%

RH

Output*

Output

%

mA

VDC*

55..............12.80.........3.20

60..............13.60.........3.40

65..............14.40.........3.60

70..............15.20.........3.80

75..............16.00.........4.00

80..............16.80.........4.20

85..............17.60.........4.40

90..............18.40.........4.60

95..............19.20.........4.80

100............20.00.........5.00

4.63“

Closure Plug

CAUTION!

See Note 2

Closure Plug

CAUTION!

See Note 2

Gasketed Cover

CAUTION!

See Note 3

2.)Unused Conduit Opening(s) Must

Have Closure Plugs Installed And Must

Be Coated with Sealing Compound To

Provide Raintight Seal. Rainwater Will

Damage Sensor!

1.)The Outside Air Sensor Must Be

Mounted In A Horizontal Position As

Shown (Sensor Tube Pointing Left

or Right with Slots Pointing Down).

Sensor Must

Be Located Where It Will Not Be

Affected By Direct Sunlight Or Heat

Producing Equipment. If Possible

Mount Under Roof Eave Or Similar

Protected Location. If Sensor Is Not

Located As Specified, Erroneous

Outside Air Humidity Readings Will

Result.

Water Must Not Be Allowed To

Stand In Sensor Tube. Rainwater

Will Damage Sensor.

0.19 Dia.

Hole Typ.

Cover

Mounting

Screw

Wiring Terminal.

Connect Wiring

To Controller Using

24 Gauge Minimum

Wire. Only 2

Conductors are

Required.

-

Typ.

Sensor Tube

CAUTION!

See Note 1

Outside Air Relative Humidity Sensor OE265-03

Mounting Bar

& Screws - Typ.

*Chart Notes:

1. Be sure that +24VDC power is being supplied to the sensor. For voltage measurement s

onnect the meter between ground and the input terminal on the controller

board that is connected to the sensor. The input on the controller board must have a 250 ohm

resistor to ground installed and have it’s associated pull-up resistor removed for the sensor to

function properly. For current measurement set the ammeter to DC Amps and connect the

meter’s lead in series with the T1 terminal on the sensor. Use an accurate humidity

measurement device to determine RH (relative humidity) such as an aspirating psychrometer.

Use the Output VDC column to read the Output Voltage or the Output mA column to read the

Output Amperage corresponding with the RH percentage measured with the psychrometer. If the

measured voltage or amperage is within 3% of what is listed for the corresponding RH, then the

sensor is functioning properly.

et the

meter to DC Volts. C

1/2

Correct

Incorrect

See Note #1

Sensor Mounting

Postion

2.88“

6.00

3.50“

3.19“

2.25“