Description

The OE511-XX-VAV Pressure Independ-
ent Round Damper consists of a round air
valve, MG320-VAV zone controller, OE282
damper actuator, airflow sensor and a
crossflow air pickup probe. An optional
auxiliary relay board (OE321) is available
for control of auxiliary heat and/or control
of series or parallel flow fan terminal units.

The MG320-VAV Zone Controller is micro-
processor based and communicates with
the HVAC Unit Controller on the WMVAV
communications loop. The VAV Controller
monitors the space temperature and allo-
cates the proper airflow into its assigned
space to achieve the desired comfort and
ventilation levels.

The Pressure Independent Round Damper
is used in systems that require pressure
independent airflow control. If your system
does not require pressure independent
control, please see the “OE510 Pressure
Dependent Round Damper” data sheet for
the correct specifications.

All Round Dampers are tested and certified in accordance with ARI standard 880. An ARI label is affixed to all
units.

Mounting

The Round Damper assembly should be mounted according to standard duct installation practices with airflow
direction as shown in the illustration above. After installation of the Round Damper in the ductwork, insulation
should be applied around any remaining uninsulated surface on the air valve inlet and outlet. The Round Damper
should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control
enclosure in a vertical plane. Do not mount the Round Damper with the control enclosure on the top or bottom of
the ductwork. Adequate clearance should be maintained between the control panel and any obstruction to allow
for removal of the control panel cover and access to the controls.

OE511-XX-VAV–Pressure

Independent Round Damper



Technical Data

OE511-XX-VAV Pressure Independent

Round Damper

VAV Controller:

Air Damper Construction:

Supply Power

24 Volt AC

Damper Body

24 Ga. Galv. Steel

Power Consumption

12 VA Maximum

Damper Blade

Round -18 Ga. Galv. Steel

Operating Temperature

35

°F to 125°F

Damper Bearings

Oil Impregnated Bronze

Operating Humidity

90% RH Non-Condensing

Damper Seal

Volara

® Type A Gasket

Communications

RS-485 - 9600 Baud

Leakage

Less Than 1% @ 3” SP

Insulation

½” Foil Faced Fiberglass

Inputs:

Dimensions:

Zone Temperature Sensor

Air Damper Model

“A”

“B”

“C”

Setpoint Adjustment

OE521-06 (6”)

19.00

5.88

9.38

Actuator Position Feedback

OE521-08 (8”)

19.00

7.88

11.38

Air Flow Sensor

OE521-10 (10”)

19.00

9.88

13.38

Outputs:

OE521-12 (12”)

22.00

11.88

15.38

Expansion Port for Auxiliary Relay Board

OE521-14 (14”)

22.00

13.88

17.38

OE521-16 (16”)

22.00

15.88

19.38

WattMaster reserves the right to change specifications without notice

Three Year Warranty On Electronic Components

One Year Warranty On Air Damper

1/2" Foil Faced

Insulation

Actuator

Zone Controller

Round Damper

Blade Assembly

Control Enclosure

(Cover Removed)

AIR

FLO

W AIR

FLO

W

Advertising
This manual is related to the following products: