3 Installation

3-1 Installation Location Considerations

Economical Series systems are portable and can be installed almost anywhere. As with
all equipment installations, follow all applicable codes and regulations.

; The recommended ambient temperature range for Economical

Series installations is from +14ºF (-10ºC) to a maximum
operating ambient temperature of 131

°F (55ºC). Recommended

ambient storage temperature range is from -13ºF to 149ºF (-
25ºC to 65ºC). If storing the unit below freezing temperatures,
make sure the unit has an antifreeze mixture circulated inside.

; Provide a minimum of twelve inches (12” or about 30 cm)

clearance on all sides of the cabinet to allow circulation of
cooling air.

; Locate the unit as close to the process as is practical.

3-2 Process Approach Temperature Considerations

If the differential (U) between

COOLING WATER IN

and

TO PROCESS

temperatures

is less than 10

°F (7ºC), consult our Sales Department for advice on how to control low

approach applications.


3-3 External Piping Sizing Considerations

; All external hose and piping should be adequately sized to

assure minimum external pressure drop.

; Low external piping pressure drop is needed for best operation.