Page 56

AEC Water Temperature Control Units

!

CAUTION

HAZARDOUS ELECTRICAL CURRENT PRESENT.

Maintain a safe ground and disconnect the power

supply before servicing the unit.

Make sure a qualified electrician makes electrical

connections; disonnect/lock out electricity using OSHA

20CFR 1910.147 standards when servicing the unit.

To adjust the pressure switch:

„ Using a small, flat-blade screwdriver, carefully remove the plug at the top
of the switch.

Figure 9

Pressure Switch

Side View and Top View


Under the plug is a Phillips-head adjusting screw:

„ Turn the screw counterclockwise to reduce the pressure.

- or -

„ Turn the screw clockwise to increase the pressure.

A quarter turn (90º rotation) approximates 15 psi (103.4 kPa/
1.0 bars).

„ Replace the plug on the top of the switch.

If the plug gets damaged, the switch is still sealed internally.

Phillips head screw