4 operating the unit with the controller, Caution – AEC Econo-Cool Chillers User Manual

Page 41

Advertising
background image

Page 40

AEC Water Temperature Control Units

!

CAUTION

1) Your system operates with hot water under pressure. To reduce the risk of

scalding:

Always wear work gloves and safety glasses when operating the unit.
Never operate the unit with panels or shields removed.
Pipe the relief valve to an open drain.
Never install a fitting or hose that is rated less than 150 psig and 250°F

(1,034.25 kPa/10.34 bars and 121ºC).

2) To reduce the risk of electrical shock:

All electrical installation and repairs should be done by a qualified

electrician.

Ground the unit in accordance with electrical codes.
Never attempt any repairs without first opening and locking out the main

disconnect.

Never deactivate or neutralize any safety device.


5-4 Operating the Unit with the Controller

To change the process temperature set point:

• Press the

Down Arrow key to lower the set point to the

temperature you want.

• Press the

Up Arrow key to raise the set point to the temperature

you want.