5-6 Checking Motor Rotation Direction

Check for correct pump rotation direction by looking at the end of the motor. Press the

ON/OFF

switch from the

OFF

( O ) position to the ON ( | ) button, and note the

direction that the motor turns. Rotation should be clockwise when viewed from the
motor end.

Note:

Make sure that a qualified electrician performs the following steps.

To change rotation direction:

1.

Disconnect and lock out power at the fused disconnect.

2.

Reverse any two incoming leads at the power terminal blocks.

3.

Do not switch leads at the motor or motor starters.

5-7 Shutting Down the Temperature Control Unit

Cool the unit down by selecting a set point of zero (

0

). Let the unit stabilize at one

temperature close to the incoming water temperature, then press the

STOP

button. Now

press the

VENT

button to relieve any remaining pressure in the system.