AEC Econo-Cool Chillers User Manual

Page 61

Advertising
background image

Page 60

AEC Water Temperature Control Units

Condition Possible

cause Solution

Undersized connectors/water
lines.

Increase size of connectors/
water lines.

Long connecting lines between
unit and mold.

Move the unit closer to the mold
and shorten connecting lines.

Serpentine flow through mold.

Connect lines for parallel flow
instead of series flow.

Blocked water line in mold.

Check mold for metal chips or
lime buildup. Clean mold.

Quick disconnect fitting with
check valve.

Remove and replace fitting or
valve.

Lime buildup in unit piping.

Clean or replace.

Faulty TCU.

Check unit by connecting ¾” line
directly from To Process to From
Process line. Run unit to
determine if TCU controls set
point temperature.

Temperature fluctuations/rapid
cycling from hot to cold.

Reversed probes.

Switch To and From Process
probes.

Drain is plugged or excessive
back pressure is in drain line.

Clear drain line or eliminate
back pressure condition.

Faulty solenoid valve.

Test solenoid valve by pressing

VENT

button and listen for valve

operation. Replace if faulty.

Controller Cool output relay
open.

Replace output relay.

Solenoid valve is not operating,
but

COOL

LED is on.

Set process temperature to
minimum and check for mag-
netism on solenoid coil top.

Solenoid coil circuit is open.

Check coil resistance. If M

range, replace solenoid coil.

Modulating valve is not
operating, but

OUT2

LED is on.

Set process temperature to
minimum and check for
complete travel of valve.

Insufficient pressure differential
between cooling

WATER IN

and

OUT

lines.

Find a means to get less back
pressure in the

WATER OUT

line.

Unit overheats or does not cool.

Cooling valve is undersize.

Replace cooling valve with a
larger valve.

Foreign material under valve
seat.

Manually open valve to clear
seat of material.

Relief valve leaks.

High system pressure.

Reduce

WATER IN

or

MAKEUP

water pressure.

Unit runs continuously cooling or
heating, and cannot attain set
point.

Unit under-sized for application.

Call sales representative.