6-5 Safety

Devices

Caution!

Make sure that only qualified electricians test safety devices!

Safety devices should be tested for function every six (6) months. Perform the
following procedures for testing:


Motor Overload

Disconnect main power. Open the electrical enclosure and rotate the manual

TEST

button on the motor overload to the tripped position. Close the enclosure and reconnect
main power. Push the

START

button. The unit should not start and the

Pump

Overload

indicator should illuminate.


Press the

RESET

button. The unit is now ready for operation.


Pressure Switch

With the unit running, program a set point of 30ºF (-1ºC). Allow the process
temperature to drop under 100ºF (38ºC). When the process temperature reaches that
point, turn off the water supply. The pump should stop and the Low Water Pressure
indicator should illuminate. Turn the water supply on to reset the pressure switch.

Adjusting the Pressure Switch

The pressure switch used in your Economical Series water temperature control unit is
factory set at 16 psig (110.3 kPa/1.1 bars). However, if the process does not require the
unit to operate at 250ºF (121ºC), you can adjust the switch to meet your process needs.

Tools Required

Small flat blade screwdriver

#2 Phillips head screwdriver