Temperature/humidity, Cleanliness – H3C Technologies H3C S5130 Series Switches User Manual

Page 9

Advertising
background image

2

To ensure correct operation and long service life of your switch, install it in an environment that meets the

requirements described in the following subsections.

Temperature/humidity

Maintain temperature and humidity in the equipment room as described in "Technical specifications."

Lasting high relative humidity can cause poor insulation, electricity creepage, mechanical property

change of materials, and metal corrosion.

Lasting low relative humidity can cause washer contraction and ESD and bring problems including
loose captive screws and circuit failure.

High temperature can accelerate the aging of insulation materials and significantly lower the
reliability and lifespan of the switch.

For the temperature and humidity requirements of different switch models, see "

Appendix A Chassis

views and technical specifications

."

Cleanliness

Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of metal

components and contact points, especially when indoor relative humidity is low. In the worst case,
electrostatic adsorption can cause communication failure.

Table 1 Dust concentration limit in the equipment room

Substance Concentration

limit (particles/m³)

Dust

≤ 3 x 10

4

(no visible dust on the tabletop over three days)

NOTE:

Dust diameter ≥ 5 μm

The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and

premature aging of components, as shown in

Table 2

.

Table 2 Harmful gas limits in the equipment room

Gas

Maximum concentration (mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01

EMI

All electromagnetic interference (EMI) sources, from outside or inside of the switch and application

system, adversely affect the switch in the following ways:

A conduction pattern of capacitance coupling.

Inductance coupling.

Advertising