Setting 1: %

The setpoint and PI monitors are displayed as a percentage with a resolution of 0.01%.

Setting 2: r/min

The setpoint and PI monitors are displayed in r/min with a resolution of 1 r/min.

Setting 3: User Defined

Parameters b5-38 and b5-39 determine the units and resolution used to display the values the setpoint in b5-19, and PI monitors

U5-01 and U5-04.

n

b5-34: PI Output Lower Limit

Sets the minimum possible PI controller output as a percentage of the maximum output frequency (E1-04). The lower limit is

disabled when set to 0.00%

No.

Name

Setting Range

Default

b5-34

PI Output Lower Limit

-100.0 to 100.0%

0.0%

n

b5-35: PI Input Limit

Sets the maximum allowed PI input as a percentage of the maximum output frequency (E1-04). Parameter b5-35 acts as a

bipolar limit.

No.

Name

Setting Range

Default

b5-35

PI Input Limit

0 to 1000.0%

1000.0%

n

b5-38, b5-39: PI Setpoint User Display, PI Setpoint Display Digits

When parameter b5-20 is set to 3, parameters b5-38 and b5-39 set a user-defined display for the PI setpoint (b5-19) and PI

feedback monitors (U5-01, U5-04).
Parameter b5-38 determines the display value when the maximum frequency is output and parameter b5-39 determines the

number of digits. The setting value is equal to the number of decimal places.

No.

Name

Setting Range

Default

b5-38

PI Setpoint User Display

1 to 60000

Determined by

b5-20

b5-39

PI Setpoint Display Digits

0 to 3

Determined by

b5-20

n

b5-40: Frequency Reference Monitor Content During PI

Sets the content of the frequency reference monitor display (U1-01) when PI control is active.

No.

Name

Setting Range

Default

b5-40

Frequency Reference Monitor Content During PI

0, 1

0

Setting 0: Frequency Reference after PI

Monitor U1-01 displays the frequency reference increased or reduced for the PI output.

Setting 1: Frequency Reference before PI

Monitor U1-01 displays the frequency reference value.

n

b5-46: PI Setpoint Monitor Unit Selection

Sets the HOA keypad display units in U5-01 and U5-04 when b5-20 is set to 3.

No.

Name

Setting Range

Default

b5-46

PI Setpoint Monitor Unit Selection

0 to 14

0

5.2 b: Application

136

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual