V/f pattern settings e1-05, 6 e: motor parameters, Setting a custom v/f pattern (setting f: default) – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 148

Advertising
background image

Predefined V/f Patterns for Models Z1B1D273 and Z1B1B124 to B302

The values in the following graphs are specific to 208 Vac. Double the values for 480 Vac.

Table 5.16 Rated Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

6

200

1.3 2.5

50

12

V

oltage (V)

Frequency (Hz)

0

6

200

1.5 3

60

12

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

60

50

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

Table 5.17 Variable Torque Characteristics, Settings 4 to 7

Setting = 4

50 Hz

Setting = 5

50 Hz

Setting = 6

60 Hz

Setting = 7

60 Hz

0

5

200

1.3

25

50

35

V

oltage (V)

Frequency (Hz)

0

6

200

1.3

25

50

50

V

oltage (V)

Frequency (Hz)

0

5

200

1.5

30

60

35

V

oltage (V)

Frequency (Hz)

0

6

200

1.5

30

60

50

V

oltage (V)

Frequency (Hz)

Table 5.18 High Starting Torque, Settings 8 to B

Setting = 8

50 Hz

Setting = 9

50 Hz

Setting = A

60 Hz

Setting = B

60 Hz

0

7

200

1.3 2.5

50

15

V

oltage (V)

Frequency (Hz)

0

9

200

1.3 2.5

50

20

V

oltage (V)

Frequency (Hz)

0

7

200

1.5 3

60

15

V

oltage (V)

Frequency (Hz)

0

11

200

1.5 3

60

20

V

oltage (V)

Frequency (Hz)

Table 5.19 Constant Output, Settings C to F

Setting = C

90 Hz

Setting = D

120 Hz

Setting = E

180 Hz

Setting = F

60 Hz

0

6

12

200

1.5 3

90

60

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

120

60

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

180

60

V

oltage (V)

Frequency (Hz)

0

6.9

230

1.5 3

60

13.8

V

oltage (V)

Frequency (Hz)

Setting a Custom V/f Pattern (Setting F: Default)

Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameter E1-05.

n

V/f Pattern Settings E1-05

If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the maximum voltage in parameters

E1-05. To create a new V/f pattern, set E1-03 to F.

No.

Parameter Name

Setting Range

Default

E1-05

Maximum Voltage

0.0 to 255.0 V

<1>

<2>

<1> Values shown are specific to 208 Vac. Double the value for 480 Vac.
<2> Default setting is determined by parameter E1-03, V/f Pattern Selection.

5.6 E: Motor Parameters

148

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual