U5: pi monitors, For a complete list of u5 – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 341

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U4-16

(7D8)

Motor Overload Estimate

(oL1)

Motor OL1 Level

Shows the value of the motor overload detection accumulator. 100% is

equal to the oL1 detection level.

10 V: 100%

0.1%

U4-18

(7DA)

Frequency Reference

Source Selection

Reference Source

Displays the source for the frequency reference as XY-nn.

X: indicates which reference is used:

0 = OFF

1 = AUTO

2 = HAND

Y-nn: indicates the reference source

0-01 = HOA keypad

1-00 = Analog (not assigned)

1-01 = Analog (terminal A1)

1-02 = Analog (terminal A2)

2-02 to 17 = Multi-step speed (d1-02 to 17)

3-01 = MEMOBUS/Modbus communications

4-01 = Communication option card

9-01 = Up/Down

No signal output

available

U4-19

(7DB)

Frequency Reference from

MEMOBUS/Modbus

Comm.

MEMOBUS Freq Ref

Displays the frequency reference provided by MEMOBUS/Modbus

(decimal).

No signal output

available

0.01%

U4-20

(7DC)

Option Frequency

Reference

Option Freq Ref

Displays the frequency reference input by an option card (decimal).

No signal output

available

U4-21

(7DD)

Run Command Source

Selection

Run Cmd Source

Displays the source for the Run command as XY-nn.

X: Indicates which Run source is used:

0 = OFF

1 = AUTO

2 = HAND

Y: Input power supply data

0 = HOA keypad

1 = External terminals

3 = BACnet or MEMOBUS/Modbus communications

4 = Communication option card

nn: Run command limit status data

00: No limit status.

01: Run command was left on when stopped in the PRG mode

02: Run command was left on when switching from LOCAL to REMOTE

operation

03: Waiting for soft charge bypass contactor after power up (Uv or Uv1

flashes after 10 s)

04: Waiting for “Run command prohibited” time period to end

05: Fast Stop (digital input, HOA keypad)

06: b1-17 (Run command given at power-up)

07: During baseblock while coast to stop with timer

08: Frequency reference is below minimal reference during baseblock

09: Waiting for Enter command

No signal output

available

U4-22

(7DE)

MEMOBUS/Modbus

Communications

Reference

MEMOBUS Ref Reg

Displays the drive control data set by MEMOBUS/Modbus

communications register no. 0001H as a four-digit hexadecimal number. No signal output

available

U4-23

(7DF)

Communication Option

Card Reference

Option Ref Reg

Displays drive control data set by an option card as a four-digit hexadecimal

number.

No signal output

available

<1> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.

u

U5: PI Monitors

No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U5-01

(57)

PI Feedback

PI Feedback 1

Displays the PI feedback value.

10 V: 100%

0.01%

U5-02

(63)

PI Input

PI Input

Displays the amount of PI input (deviation between PI setpoint and

feedback).

10 V: 100%

0.01%

B.13 U: Monitors

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

341