4.7 Absolute Encoders

4-39

4

Ope

rat

ion

4.7.2 Absolute Data Request (SENS ON Command)

The Turn Encoder Power Supply ON command (SENS_ON) must be sent to obtain absolute data as an output

from the SERVOPACK.

The SENS_ON command is sent at the following timing.

∗ Send the SENS_OFF command to turn OFF the control power supply.

SERVOPACK control
power supply

5 seconds max.

ON

OFF

OFF

ON (Normal status)

OFF

ON

50 ms

Rotational serial data

(Phase A)

(Phase B)

(Phase B)

Approx.
15 ms

400 ms max.

1 to 3 ms

60 ms max.
(90 ms typ.)

The servomotor will not be turned ON even if the SV_ON command is received during this interval.

ALM signal OFF
(Alarm status)

SENS_ON
(Turn Encoder Power
Supply ON)

PAO

PBO

Servomotor power

Undefined

Undefined

(Phase A)

OFF

OFF

OFF

OFF

*

ON

Incremental
pulses

Incremental
pulses

Initial incremental
pulses

Initial incremental
pulses

46