9 Troubleshooting

9.1.2 Troubleshooting of Alarms

9-16

A.b6b:
MECHATROLINK

Communications ASIC

Error 2

MECHATROLINK data recep-

tion error occurred due to noise
interference.

Take measures against noise. Check
the MECHATROLINK communi-
cations cable and FG wiring and
take measures such as adding ferrite

core on the MECHATROLINK
communications cable.

SERVOPACK MECHA-
TROLINK communication sec-
tion fault.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

A.bF0:
System Alarm 0

A SERVOPACK fault occurred.

Turn the power supply OFF and

then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

A.bF1:
System Alarm 1

A SERVOPACK fault occurred.

Turn the power supply OFF and
then ON again. If the alarm still

occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

A.bF2:
System Alarm 2

A SERVOPACK fault occurred.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

A.bF3

:

System Alarm 3

A SERVOPACK fault occurred.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

A.bF4:
System Alarm 4

A SERVOPACK fault occurred.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

A.C10:
Servo Overrun Detect-

ed
(Detected when the
servomotor power is
ON.)

The order of phases U, V, and W
in the servomotor wiring is incor-
rect.

Check the motor wiring.

Confirm that the servomotor is cor-
rectly wired.

An encoder fault occurred.

If the alarm still occurs after turning
the power OFF and then ON again,
even though the servomotor is cor-
rectly wired, the servomotor may be
faulty. Replace the servomotor.

A SERVOPACK fault occurred.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

A.C80:
Absolute Encoder

Clear Error and Multi-

turn Limit Setting Error

An encoder fault occurred.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the servomotor may be
faulty. Replace the servomotor.

A SERVOPACK fault occurred.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

(cont’d)

Alarm Number:

Alarm Name

(Alarm Description)

Cause

Investigative Actions

Corrective Actions