3.2 Wiring the MPX

This section covers installing AC, DC, and communication wiring for each MPX model (Table 3-1).

TABLE 3-1, MPX WIRING TABLE

MPX Model

MP Enclosure

Used With:

Inverter

AC Wiring

External*

AC Wiring

Inverter

DC Wiring

Battery Bank

DC Wiring

Communica-

tions Wiring

MPXS-30D

MPSL-30D

Figure 3-18a

Figure 3-18b

Figure 3-18c

Figure 3-18d

Figure 3-18e

MPXS-30D

MPSH-30D

Figure 3-19a

Figure 3-19b

Figure 3-19c

Figure 3-19d

Figure 3-19e

MPXS-60S

MPSL-60S

Figure 3-21a

Figure 3-21b

Figure 3-21c

Figure 3-21d

Figure 3-21e

MPXD-30D

MPDH-30D

Figure 3-22a

Figure 3-22b

Figure 3-22c

Figure 3-22d

Figure 3-22e

*- ‘External’ refers to wiring that is required outside the MP/MPX panel (i.e., wiring to loads, grid/gen input wiring)

3.2.1 Wiring Guidelines

This section provides general information on the AC wiring to/from the new inverter, from the incom-

ing AC source, and to the outgoing AC distribution panel (i.e., inverter sub-panel).
IMPORTANT: All wiring should meet local codes and standards and be performed by quali-

fi ed personnel such as a licensed electrician.

CAUTION: Before installing any AC wiring, review all safety information in the MP Owner’s

Manual (PN: 64-0028) and at the beginning of this manual, and the information below

to ensure a safe system:
• The AC wires must be appropriately sized, and must be no less than #10 AWG (5.3

mm

2

) gauge copper wire and be approved for residential wiring.

• DO

NOT connect the Magnum inverter’s output to an AC power source. This could

cause severe damage to the inverter and is not covered under warranty.

WARNING: To reduce the risk of fi re, do not connect a 120V AC only inverter to both

busbars in an AC load center (circuit breaker panel) having multi-wire branch circuits

connected. Every circuit connected to a 120V AC panel must have its own neutral; other-

wise, currents on shared neutrals will add rather than subtract – overloading the neutral

conductor.

The AC and DC wires into and out of the MP enclosure and the MPX extension must be protected as re-
quired by code. This can be done by using jacketed wires or by feeding wires through conduit.

Info: If using a Magnum inverter, and the AC wires are individual conductors (i.e., not

jacketed), the strain reliefs on the inverter can be replaced with 3/4” grommets.

• Use proper clamps or other approved methods for securing the cable/conduit to the enclosure.
• The MP enclosure is specifi cally approved/designed for both AC and DC wiring. However, where

DC wiring must cross AC or vice-versa, try to make the wires at the crossing point 90° to one

another.

• Use only copper wires with a minimum rating of 150V, 75°C if only 120V AC power is being used;

or, with a minimum rating of 300V, 75°C if 120/240V AC power is being used.

• In a system where one conductor is grounded, the wire colors on the DC side and the AC side

are the same. The insulation on all grounded conductors (DC negative/AC neutral) must be

white, gray, or any color except green if marked with white at each termination (marking only

allowed on 6 AWG or larger conductors). The equipment grounding conductors must be bare

(no insulation), or have green or green with yellow-striped insulation or identifi cation. The hot

ungrounded conductor (DC positive/AC hot) is usually red or black.

• Terminals containing more than one conductor must be listed for multiple conductors.
• The connectors or terminals used on fl exible, fi ne-stranded conductors must be specifi cally

marked or labeled for use with fi ne-stranded conductors.

• The MPX/MP enclosures include wires (along with communication cables) with insulation rated for

at least 300 volts, which allows 120/240V AC inverters to be installed. If installing a 120/240V

AC inverter, the installer must also provide wires (both power and communication) with the

insulation rated for at least 300 volts.