0 installation, Figure 3-17, dc cable connections – Magnum Energy MP Extension Box (MPX Series) User Manual

Page 23

Advertising
background image

3.0 Installation

© 2011 Magnum Energy, Inc.

19

Inverter Hardware Stack-up:

Inverter DC terminals
Inverter cable lugs

[(-) to shunt busbar,

(+) to inverter DC breaker]
5/16-18 nut (Flange or Kep)

DO NOT place anything

between the inverter DC

terminals and the inverter

cable lugs.

1

2

3

Top of Shunt Busbar Hardware

Stack-up:

DC shunt busbar (top)
Hex bolt (3/8-16-3/4")
Negative (-) battery cable lug
Split-lock washer
3/8-16 nut

DO NOT place anything

between the DC shunt busbar

and the negative inverter cable

lug.

1

2

3

4
5

Top of DC Breaker Hardware

Stack-up:

DC breaker (top) terminal
Positive (+) inverter cable lug
Split-lock washer
Hex bolt (3/8-16-3/4")

DO NOT place anything

between the DC breaker

terminal and the positive

inverter cable lug.

1

2
3

4

Bottom of DC Breaker Hardware

Stack-up:

DC breaker (bottom) terminal
Positive (+) battery cable lug
Split-lock washer
Hex bolt (3/8-16-3/4")

DO NOT place anything

between the DC breaker

terminal and the positive

battery cable lug.

Bottom of Shunt Busbar

Hardware Stack-up:

DC shunt busbar (bottom)
Hex bolt (3/8-16-3/4")
Negative (-) battery cable lug
Split-lock washer
3/8-16 nut

DO NOT place anything

between the DC shunt busbar

and the negative battery cable

lug.

1

2

3

4

4

3

2

1

5

3

1

2

3

4

5

2

1

2

1

3 4

2

1

3 4

1

3 4 5

2

MPX

MP

Enclosure

Inverter

#2

Inverter

#1

Figure 3-17, DC Cable Connections

I

NVERTER

DC N

EGATIVE

AND

P

OSITIVE

C

ONNECTIONS

I

NVERTER

N

EGATIVE

TO

S

HUNT

B

USBAR

(T

OP

) DC P

OSITIVE

C

ONNECTION

I

NVERTER

P

OSITIVE

TO

I

NVERTER

DC B

REAKER

(T

OP

) C

ONNECTION

B

ATTERY

P

OSITIVE

TO

I

NVERTER

DC B

REAKER

(B

OTTOM

) C

ONNECTION

B

ATTERY

N

EGATIVE

TO

S

HUNT

B

USBAR

(B

OTTOM

) C

ONNECTION

Advertising