Magnum Energy MP Extension Box (MPX Series) User Manual

Page 9

Advertising
background image

2.0 Introduction

© 2011 Magnum Energy, Inc.

5

2.2 Available MPX Models

The three models in the MPX Series are: the MPXS-30D, MPXS-60S, and the MPXD-30D (see Figures 2-3

to 2-5). The MPXS-30D model is designed for use with a single MP enclosure (MPSL-30D and MPSH-

30D), the MPXS-60S is only used with the MPSL-60S, while the MPXD-30D is designed for use with

a dual MP enclosure (MPDH-30D). Each model comes in a left (L) and right (R) version. The ‘right’

version (MPXS-30D-R, MPXS-60S-R, or MPXD-30D-R) is used when the MPX is mounted to the right

of the MP enclosure, and the ‘left’ version (MPXS-30D-L, MPXS-60S-L, or MPXD-30D-L) is used when

the MPX is mounted to the left of the MP enclosure. The left version differs from the right only in that

the length of the supplied DC cables are different to accommodate the difference in distance from

the MP’s DC breaker to the new installed inverter.

Info: The MPXS-60S model is unique in that it provides #6 AC wiring and a single-pole

60 AAC breaker, rather than the #10 AC wiring and 30 AAC double-pole breaker that

comes with the MPXS-30D and MPXD-30D models.

TABLE 2-3, MPX MODELS

MPX

Model

Versions

(left or right installation)

Used With:

MP Enclosure

Inverters

MPXS-30D

MPXS-30D-L/MPXS-30D-R

MPSL-30D/MPSH-30D

MS4024PAE or MS4448PAE

stacked in parallel

MPXS-60S

MPXS-60S-L/MPXS-60S-R

MPSL-60S

MS4024 stacked in series

MPXD-30D

MPXD-30D-L/MPXD-30D-R

MPDH-30D

MS4024PAE or MS4448PAE

stacked in parallel

TABLE 2-2, DC 2/0 BATTERY CABLE LENGTHS

Model

Black Cable

Red Cable

MPXS-30D-L

23.25”

21.00”

MPXS-30D-R

15.25”

16.50”

MPXS-60S-L

23.25”

21.00”

MPXS-60S-R

15.25”

16.50”

MPXD-30D-L

39.00”

26.75”

MPXD-30D-R

14.75”

24.25”

MPSL-60S

MPXS-60S-L

MPSL-60S

MPXS-60S-R

OR

MPXS-60S on left side (MPXS-60S-L)

MPXS-60S on right side (MPXS-60S-R)

MS4024

I

NVERTER

MS4024

I

NVERTER

MS4024

I

NVERTER

MS4024

I

NVERTER

Figure 2-3, MPXS-60S Installation Confi gurations

Advertising