Magnum Energy MP Extension Box (MPX Series) User Manual

Page 38

Advertising
background image

3.0 Installation

© 2011 Magnum Energy, Inc.

34

MS4024 Series Inverter (LEG 2) –

showing AC wires from the

internal AC wiring terminal

30

Left side view of

inverter mounted

on MPX Enclosure

Inverter AC

Input Wires

(Leg 2 Only)

Inverter AC

Output Wires

(Leg 2 Only)

AC

GROUND

.

AC HOT 2 OUT

.

AC NEUT IN

.

AC NEUT OUT

.

AC HOT 1 OUT

.

AC HOT 1 IN

.

AC HOT 2 IN

.

RED

.

WHI

T

E

.

RED w/

STRI

PE

.

W
H

IT

E w/

STRI

PE

.

GREEN

See NOTE

below

Info: When wiring the MS4024 (or any other MS Series inverter), both the inverter input

and output neutral wires must be connected to a AC NEUTRAL busbar inside the MP en-

closure. This is because — depending on the inverter’s operating mode — the inverter’s

input and output neutral terminals may not be connected together (i.e., inverter’s neu-

trals are not connected when “inverting”, and are combined when “charging”).

NOTE: Because a neutral to ground connection is also made in the MP enclosure, the neutral to

ground connection inside the MS4024 must be disconnected. Refer to your MS4024 owner’s manual

for information on how this is done.

Figure 3-20a, Inverter AC Input and Output Wiring Diagram