3.2.4 Wiring the MPXD-30D

The following steps are basic guidelines for installing and connecting the AC, DC, and communica-

tion wiring for the MPXD-30D.

WARNING: To prevent electrical shock, make sure all AC power (inverter, generator, or

utility) is off before making any AC connections inside the MP enclosure.

MPXD-30D AC Wiring

This section provides information on the AC wiring to/from the MS-PAE Series inverters, and to/

from the main and sub-panels.
Inverter AC Input Wiring (see Figures 3-22a.1 and 3-22a.2)
1. Route and attach a black wire from the top right terminal of the new AC input breakers (left MP

enclosure) to each inverter’s AC HOT 1 IN terminal.

2. Route and attach a red wire from the top left terminal of the new AC input breakers to each

inverter’s AC HOT 2 IN terminal.

3. Route and attach a green wire from the left MP enclosure’s GROUND busbar to each inverter’s

AC GROUND terminal.

Inverter AC Output Wiring (see Figures 3-22a.1 and 3-22a.2)
1. Route and attach a black w/white stripe wire to each inverter’s AC HOT 1 OUT terminal from the

left MP enclosure’s INV HOT 1 OUT busbar.

2. Route and attach a red w/white stripe wire to each inverter’s AC HOT 2 OUT terminal from the

left MP enclosure’s INV HOT 2 OUT busbar.

3. Route and attach a white wire from the left MP enclosure’s AC NEUTRAL busbar to each inverter’s

AC NEUTRAL terminal.

Bottom AC Breaker Wiring (see Figure 3-22b)
1. Route and attach a black wire to the left MP enclosure’s AC LEG 1 IN busbar from the bottom

right terminal of each of the new AC input breakers.

2. Route and attach a red wire to the left MP enclosure’s AC LEG 2 IN busbar from the bottom of

each of the new AC input breakers.

External AC Main Panel Wiring (see Figure 3-22b)
1. Route and attach a black wire to the left MP enclosure’s AC LEG 1 IN busbar from the main AC

electrical panel.

2. Route and attach a red wire to the left MP enclosure’s AC LEG 2 IN busbar from the main AC

electrical panel.

3. Route and attach a green wire to the left MP enclosure’s GROUND busbar from the main AC

electrical panel’s Ground busbar.

4. Route and attach a white wire to the left MP enclosure’s AC NEUTRAL busbar from the main AC

electrical panel’s Neutral busbar.

External AC Sub-Panel Wiring (see Figure 3-22b)
1. Route and attach a black wire from the left MP enclosure’s AC LEG 1 OUT busbar to the AC

electrical sub-panel.

2. Route and attach a red wire from the left MP enclosure’s AC LEG 2 OUT busbar to the AC

electrical sub-panel.

3. Route and attach a green wire from the left MP enclosure’s GROUND busbar to the AC electrical

sub-panel’s Ground busbar.

4. Route and attach a white wire from the left MP enclosure’s AC NEUTRAL busbar to the AC

electrical sub-panel’s Neutral busbar.

AC Wiring Inspection
After verifying all AC connections are correct and all AC terminal screws are torqued correctly,