CAC CASSETTE EVAPORATOR INSTALLATION INSTRUCTIONS

4. Slide cover

up and out

to remove.

All wiring should be in accordance with

the National Electric Code (NEC) and the

local building codes.
1. Make sure power is off.

2. Inspect the existing wiring for any de-

fi ciencies such as cut or frayed wires.

Replace if any such wiring if found.

3. Remove the 4 screws securing the

control box cover.

The standard unit Voltage is 208/230V

(60Hz, 1Ph). Check the unit’s rating plate

for your models’ electrical requirements.

• The wires should be capable of carry-

ing the maximum load current under

non-fault conditions at the stipulated

Voltages.

• Avoid large Voltage drops on cable

runs, particularly in low Voltage wir-

ing.

• The correct cable size must be used to

ensure a Voltage drop of less than 1

Volt in the control wiring.

• Once the refrigeration pipe work is

complete, the electrical supply can be

connected.

• Low Volt wiring must be at least 18 awg.

Electrical Wiring

5. The rating plate is located on the outside

of control box cover (see Low Volt Inter-

connecting Wiring section for location of

wiring diagram).

6. Check the unit rating plate for circuit

ampacity and breaker or fuse size.

Use

only HACR type breakers. Select the

proper wire for the ampacity rating.

7. Each unit must have a separate branch

circuit protected by a fuse or breaker.

Refer to the unit rating plate for the

proper wire and breaker or fuse size.

8. It is also recommended that a local dis-

connect switch be connected within 3’

of the unit. In some areas this may be a

code requirement.